Speed And Torque Control Using Abb Drives; Communication Profile With Parameter-Configured Pdo; Mapping - ABB FCAN-01 User Manual

Canopen adapter module
Table of Contents

Advertisement

The start sequence for the parameter example above is given
below.
Control word:
Reset the fieldbus communication fault (if active).
7Fh → Operation enabled = Drive starts modulating
77h → Disable operation = Ramp stop (possible to restart
during ramping)
7Eh → Switch on disabled = Coast stop
7Bh → Quick stop = Emergency stop (not possible to restart
during ramping)

Speed and torque control using ABB Drives

communication profile with parameter-configured PDO

mapping

This example shows how to configure a speed and torque control
application that uses the ABB Drives profile. In addition, some
application specific data is added to the communication.
The start/stop commands and references are according to the ABB
Drives profile. (For more information, see section
communication profile
When reference 1 (REF1) is used, reference value ±20000
(decimal) corresponds to the reference set with parameter 1105
REF1 MAX in the forward and reverse directions.
When reference 2 (REF2) is used, a reference value of ±10000
(decimal) corresponds to the reference set with parameter 1108
REF2 MAX in the forward and reverse directions.
The minimum and maximum 16-bit integer values that can be
given through the fieldbus are -32768 and 32767 respectively.
PDO
Word 1
Rx PDO1
6040h
Control
1)
word
Tx PDO1
6041h
Status
1)
word
on page 100.)
Word 2
Word 3
6042h
2000h03
Target
Reference
1)
1)
velocity
2
6044h
2000h06
vl control
Actual value
1)
1)
effort
2
Start-up 61
ABB Drives
Word 4
Length
4001h23
64 bits
Par. 0135
COMM
2)
VALUE 1
4001h06
64 bits
Par. 0106
2)
POWER