104 Communication profiles
Status word of ABB Drives profile
Bit
Name
10
ABOVE_
LIMIT
11
EXT_CTRL_
LOC
12
EXT_RUN_E
NABLE
13...14 Reserved
15
FBA_ERROR
Value
STATE/Description
1
Actual frequency or speed equals or
exceeds the supervision limit (set with
the drive parameter). Valid in both
directions of rotation.
0
Actual frequency or speed within
supervision limit
1
External Control Location EXT2
selected
Note concerning ACS880: This bit is
effective only if the fieldbus interface is
set as the target for this signal by drive
parameters. User bit 0 selection
(06.33).
0
External Control Location EXT1
selected
1
External Run Enable signal received
Note concerning ACS880: This bit is
effective only if the fieldbus interface is
set as the target for this signal by drive
parameters. User bit 1 selection
(06.34).
0
No External Run Enable signal
received
1
Communication error detected by the
fieldbus adapter module.
0
Fieldbus adapter communication OK