ABB FCAN-01 User Manual page 41

Canopen adapter module
Table of Contents

Advertisement

No.
Name/Value
06
T16 scale
0...65535
Description
Defines the reference multiplier/actual value
divisor for the adapter module. The parameter
is effective only when the Transparent 16 profile
is selected AND the drive is using the native
communication profile (for example, DCU or
FBA) and a 16-bit transparent Reference
1/Actual value 1.
With an ACS355 drive, the speed reference
from the PLC is multiplied by the value of this
parameter plus one. For example, if the
parameter has a value of 99 and a reference of
1000 given by the master, the reference will be
multiplied by 99 + 1 = 100 and forwarded to the
drive as 100000. According to the DCU profile,
this value is interpreted as a reference of 100
rpm in the drive.
With ACSM1, ACS850 and ACS880, setting
this parameter to 65535 provides the
approximation of 1 ≈ 1 rpm.
Reference multiplier/actual value divisor
Start-up 41
Default
setting
99

Advertisement

Table of Contents
loading

Table of Contents