ABB FCAN-01 User Manual page 135

Canopen adapter module
Table of Contents

Advertisement

Index
Sub-
Name
(hex)
index
1010
0
Store
Parame-
ters
1
2
3
4
Type
Attri-
Information
bute
U32
RO
Largest supported subindex.
Subindex 1...n bit 0 value 1
indicates that the device can
save the parameters in
question. Parameters can be
saved by writing 65766173h
("evas") to the appropriate
subindex.
U32
RW
Saves all parameters.
U32
RW
Saves communication
parameters (1000h...1FFFh).
U32
RW
Saves application parameters
(6000h...9FFFh).
Note: Some of the application
parameters are associated
with drive parameters. After
application parameters have
been saved, FCAN-01
overwrites these drive
parameters when it is powerd
up or fieldbus parameter are
refreshed. This can be
reversed by setting the
application parameters to
default values with object
0x1011.
U32
RW
Requests the drive to perform
the parameter save function.
Refer to the drive manual for
more information.
Communication protocol 135

Advertisement

Table of Contents
loading

Table of Contents