Starting up ACS880 drives

1. Power up the drive.
2. Enable the communication between the adapter module and
the drive by setting parameter 50.01 FBA A enable to Enable.
3. With parameter 50.02 FBA A comm loss func, select how the
drive reacts to a fieldbus communication break.
Note: This function monitors both communication between the
fieldbus master and adapter module and communication
between the adapter module and drive.
4. With parameter 50.03 FBA A comm loss t out, define the
time between communication break detection and the selected
action.
5. Select application-specific values for parameters
50.04...50.11. Examples of appropriate values are shown in
the tables below.
6. Set the FCAN-01 configuration parameters in drive parameter
group 51.
At minimum, set the required node address in parameter 51.02
Node ID, the required bit rate in 51.03 Bit rate, select source
of the PDO configuration in 51.04 Conf location and the
communication profile in 51.05 Profile.
7. If the group 51 is selected as the source for the PDO
configuration, select the application specific configuration for
the PDOs with parameters 51.07...51.24.
8. Define the process data transferred to and from the drive in the
FCAN-01 configuration parameter groups 52 and 53.
Note: If the PDO configuration is written from the PLC, the
parameters 51.07...51.24 are not used and the parameter
groups 52 and 53 display the process data selected in the
PLC.
Start-up 75