Siemens 6RA7086-6KS22 Operating Instructions Manual page 558

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

Parameter list
PNU
Description
11.46 Profile parameters
P918
CB bus address
Protocol-dependent bus address for communication boards
(Z110)
(Z111)
Note:
The validity of the bus address is monitored by the communication board.
(Bus addresses 0 to 2 are reserved for Master stations on PROFIBUS
boards and must not therefore be set for other purposes). If the value is not
accepted by the COM BOARD, fault F080 is displayed with fault value 5
P927
Parameterization enable
*
Enabling of interfaces for parameterization. A parameter value can only be
(G170)
altered via an enabled interface.
(G171)
(G172)
0:
None
1:
Communications board (CB)
(Z110)
2:
Parameterizing unit (PMU)
(Z111)
4:
G-SST1 serial interface and OP1S
8:
Reserved
16:
Technology board (TB)
32:
G-SST2 serial interface
64:
G-SST3 serial interface
Setting information:
Every interface has a numeric code.
The number for one specific interface, or the sum of various numbers
assigned to several interfaces, must be entered in this parameter in order to
enable the relevant interface(s) for use as a parameterization interface.
Example:
Factory setting value 6 (=4+2) means that the PMU and G-SST1 interfaces
are enabled for parameterization purposes.
11-94
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
0 to 200
Ind: 2
1
FS=3
Type: O2
0 to 127
Ind: None
1
FS=6
Type: V2
SIEMENS AG
SIMOREG DC Master
Operating Instructions
05.05
See
Change
(Access /
Status)
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
6RX1700-0AD76

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents