05.05
PNU
Description
P430
Source for fixed-setpoint injection
*
Selection of binector to control injection of the fixed setpoint
("1" state = fixed setpoint injected).
(G127)
0 = binector B0000
1 = binector B0001
etc.
P431
Source for fixed setpoint
*
Selection of connector to be injected as the fixed setpoint
(G127)
0 = connector K0000
1 = connector K0001
etc.
P432
Source for selection of ramp-function generator bypass
*
Selection as to whether or not ramp-function generator must be bypassed
when the fixed setpoint is injected.
(G127)
The ramp-function generator is bypassed if the AND operation between the
binector selected via an index of P430 and the setting in the same index of
P432 produces a log. "1"
P433
Source for standard setpoint
*
Selection of the connector to be applied if fixed-setpoint injection is not
FDS
selected
0 = connector K0000
(G127)
1 = connector K0001
etc.
Inching setpoint
Function: Up to 8 connectors can be selected in P436 indices .01 to .08. These can be applied as an inching setpoint (K0202, K0207) via
the binectors selected in P435, indices .01 to .08 (setpoint is applied when binector switches to log. "1" state). P437 indices .01
to .08 can be set to define for each setpoint individually whether the ramp-function generator must be bypassed on setpoint
injection. If more than one inching setpoint is injected, an output value corresponding to inching setpoint = 0% is applied.
If inching setpoint injection is not selected, the connector set in P438 is applied to K0207.
P435
Source for injection of inching setpoint
*
Selection of binector to control injection of the inching setpoint
("1" state = inching setpoint injected).
(G129)
0 = binector B0000
1 = binector B0001
etc.
P436
Source for inching setpoint
*
Selection of connector to be injected as the inching setpoint
(G129)
0 = connector K0000
1 = connector K0001
etc.
P437
Source for selection of ramp-function generator bypass
*
Selection as to whether or not ramp-function generator must be bypassed
when the inching setpoint is injected.
(G129)
The ramp-function generator is bypassed if the AND operation between the
binector selected via an index of P435 and the setting in the same index of
P437 produces a log. "1".
P438
Source for standard setpoint
*
Selection of the connector to be applied if inching-setpoint injection is not
FDS
selected
0 = connector K0000
(G129)
1 = connector K0001
etc.
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
All binector numbers
Ind: 8
1
FS=0
Type: L2
All connector
Ind: 8
numbers
FS=0
1
Type: L2
0 to 1
Ind: 8
1
FS=0
Type: O2
All connector
Ind: 4
numbers
FS=11
1
Type: L2
All binector numbers
Ind: 8
1
FS=0
Type: L2
All connector
Ind: 8
numbers
FS=0
1
Type: L2
0 to 1
Ind: 8
1
FS=0
Type: O2
All connector
Ind: 4
numbers
FS=208
1
Type: L2
Parameter list
See
Change
(Access /
Status)
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
11-49