05.05
PNU
Description
11.5
Definition of SIMOREG DC MASTER power section
P067
Load class
*
1
Load class DC I
2
Load class DC II
(G101)
3
Load class DC III
4
Load class DC IV
5
US rating
The load classes are described in Chapter 3.4.1.
Depending on the load class selected, the device rated DC of the
SIMOREG DC Master is reduced to a value of different magnitude to suit
the power section and load class.
The current value of the device rated DC is indicated in parameter r072.002.
Notes:
If the device rated DC is reduced via parameter P076.001, the lesser of the
two values is active.
If you set a value of > 1 in P067, you must ensure that the "Dynamic
overload capability of power module" is enabled, i.e. a value of > 0 must be
set in parameter P075.
The SIMOREG DC Master does not monitor for compliance with the criteria
of the load class set in parameter P067. If permitted by the power module,
the unit can operate for overload periods in excess of those defined by the
load class. The permissible overload period for the installed power module
is always longer than the period defined for the load class. The SIMOREG
DC Master does monitor the actual permissible overload period for the
power module. See Section 9.15.
r068
Options according to rating plate
0
No option
(G101)
1
Option L04 (low voltage, 85V)
2
Option K00 (terminal expansion)
3
L04 and K00
r069
Serial number of SIMOREG DC Master converter
st
i001:
1
and 2
(G101)
rd
i002:
3
and 4
th
i003:
5
and 6
th
i004:
7
and 8
th
i005:
9
and 10
th
i006:
11
and 12
th
i007:
13
and 14
i008 to i015:
i016:
Checksum for serial number
The serial number ASCII code is displayed in this parameter. The number is
output in plaintext on the OP1S panel.
r070
MLFB (order number) of SIMOREG DC Master converter
The corresponding MLFB is displayed in encoded form in this parameter.
(G101)
The MLFB is displayed in plaintext on the OP1S panel.
r071
Converter rated supply voltage (armature)
Converter rated supply voltage (armature) as specified on rating plate
(G101)
r072
Converter rated DC current (armature)
i001:
Converter rated DC current (armature) as specified on rating
(G101)
plate (output DC current at power terminals 1C1 and 1D1)
i002:
Actual converter rated DC current (armature) according to
setting in parameter P076.001 or P067
r073
Converter rated DC current (field)
i001:
Converter rated DC current (field) as specified on rating plate
(G101)
(output DC current at power terminals 3C and 3D)
i002:
Actual converter rated DC current (field) as set in parameter
P076.002
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
nd
places of serial number
th
places of serial number
th
places of serial number
th
places of serial number
th
places of serial number
th
places of serial number
th
places of serial number
0
Value range
[Unit]
Steps
[SW1.8 and later]
1 to 5
1
0 to 120
1
10 to 1000
[V]
1V
0.0 to 6553.5
[A]
0.1A
0.00 to 100.00
[A]
0.01A
Parameter list
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: None
P052 = 3
FS=1
P051 = 40
Type: O2
Offline
Ind: None
P052 = 3
Type: 02
Ind: 16
P052 = 3
Type: L2
Ind: None
P052 = 3
Type: O2
Ind: None
P052 = 3
Type: O2
Ind: 2
P052 = 3
Type: O2
Ind: 2
P052 = 3
Type: O2
11-15