Siemens 6RA7086-6KS22 Operating Instructions Manual page 635

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

05.05
PNU
Description
11.89 Configuration of paralleling interface
Notes about parameterization of the paralleling interface see Chapter 6.3.2
U800
Control word for paralleling interface
(2800)
0:
Paralleling interface not active
*
1:
Paralleling interface active
The gating pulses are generated by this SIMOREG converter
2:
Paralleling interface active
(G195)
The gating pulses of the master are used
Must also be set if a SIMOREG CCP is used
U803
Operating mode for the parallel connection
(2803)
0
Standard mode
*
All parallel-connected SIMOREG devices must be in continuous
operation. Failure (fault message, fuse blown) of one of the
(G195)
parallel-connected SIMOREG devices causes immediate pulse
disabling for all SIMOREG devices.
1
"N+1 mode" (redundancy mode)
On failure (fault message, fuse blown) of one of the parallel-
connected SIMOREG devices, operation is maintained with the
remaining SIMOREG devices.
U804
Transmit data on paralleling interface
(2804)
Selection of connectors whose contents must be injected as transmit data
*
(master to slaves or slave to master) for the paralleling interface.
0 = connector K0000
(G195)
1 = connector K0001
etc.
This parameter not only defines the transmit data, but also their position in
the transmit telegram.
i001:
Word 1 of telegram
...
i005:
Word 5 of telegram
i006:
word 1 of the telegram, if "standby master"
...
i010:
word 5 of the telegram, if "standby master"
Indices .06 to .10 of U804 are activated on the master and the standby
master when the "master" function is transferred to the standby master
U805
Control word for bus terminator of paralleling interface
(2805)
0:
No bus terminator
(G195)
1:
Bus terminator active
U806
Address for the parallel connection of SIMOREG devices
(2806)
i001:
Address of the masters or of the slaves
*
i002:
Address of the "standby master" or slaves
2:
Slave device with address 2
(G195)
3:
Slave device with address 3
4:
Slave device with address 4
5:
Slave device with address 5
6:
Slave device with address 6
12:
Master device for 1 slave device with address 2
13:
Master device for 2 slave devices with addresses 2 and 3
14:
Master device for 3 slave devices with addresses 2, 3 and 4
15:
Master device for 4 slave devices with addresses 2, 3, 4 and 5
16:
Master device for 5 slave devices with addresses 2, 3, 4, 5 and
6
In "Standard" mode (U803 = 0), i001 and i002 must be set to the same
value.
In "N+1 mode" (U803 = 1), a SIMOREG device has the "master" function, a
SIMOREG device has the "standby Master" function and all other devices
are slaves. In the slaves, i001 and i002 must be set to the same value.
On the master, a value of 12 to 16 must be set in i001, in i002 a value of 2
to 6.
In the "standby master", a value of 2 to 6 must be set in i001, in i002 a value
of 12 to 16.
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Value range
[Unit]
Steps
0 to 2
1
0 to 1
[SW 1.7 and later]
1
All connector
numbers
1
[SW 1.7 and later]
[SW 1.7 and later]
0 to 1
1
see column on left
[SW 1.7 and later]
Parameter list
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: None
P052 = 3
FS=0
P051 = 40
Type: O2
Offline
Ind: None
P052 = 3
FS=0
P051 = 40
Type: O2
off-line
Ind: 10
P052 = 3
FS=0
P051 = 40
Type: L2
Online
Ind: None
P052 = 3
FS=0
P051 = 40
Type: O2
Online
Ind: 2
P052 = 3
FS=2
P051 = 40
Type: O2
off-line
11-171