List of connectors and binectors
12.1

Connector list

The values of connectors can be displayed via parameters r041, r042, r043 and P044.
The following numeric representation applies to all connectors:
In the internal software representation, 100% corresponds to the number 4000 hex = 16384 dec. The
value range is -200.00% ... +199.99%, corresponding to 8000 hex ... 7FFF hex. The connectors are
transferred via the serial interfaces in this internal mode of representation.
100% corresponds to converter rated quantities r072.i02 (currents, armature), r073.i02 (currents,
field), P078.i01 (line voltages, armature).
The following numeric representation applies to all double-word connectors:
In the internal software representation, 100% corresponds to the number 4000 0000 hex =
16384*65536 dec.
The value range is -200.00% ... +199.9999999%, corresponding to -2
8000 0000 hex ... 7FFF FFFF hex.
If a double-word connector is the input of a connector selection parameter, or if a connector is the
input of a double-word connector selection parameter, this may be equivalent to division or
multiplication by the value 65536. For details of the connection to double-word connectors, see
Section 9.1, "The following rules apply to the selection of double-word connectors".
Connector
Description
Fixed values
K0000
Fixed value 0
Fixed value 100.00%
K0001
K0002
Fixed value 200.00%
K0003
Fixed value -100.00%
K0004
Fixed value -200.00%
Fixed value 50.00%
K0005
Fixed value 150.00%
K0006
K0007
Fixed value -50.00%
K0008
Fixed value -150.00%
K0009
Fixed value 0 or special function specified in each case
Analog inputs
Analog input, terminal 4 / 5 (main setpoint)
K0010
Raw value after A/D conversion (unfiltered, not normalized)
Analog input, terminal 4 / 5 (main setpoint)
K0011
After normalization, offset injection, filtering
Analog input, terminal 103 / 104 (main actual value)
K0012
Raw value after A/D conversion (unfiltered, not normalized)
K0013
Analog input, terminal 103 / 104 (main actual value)
After normalization, offset injection, filtering
K0014
Analog input, terminal 6 / 7 (analog selectable input 1)
Raw value after A/D conversion (unfiltered, not normalized)
K0015
Analog input, terminal 6 / 7 (analog selectable input 1)
After normalization, offset injection, filtering
K0016
Analog input, terminal 8 / 9 (analog selectable input 2)
Raw value after A/D conversion (unfiltered, not normalized)
K0017
Analog input, terminal 8 / 9 (analog selectable input 2)
After normalization, offset injection, filtering
K0018
Analog input, terminal 10 / 11 (analog selectable input 3)
Raw value after A/D conversion (unfiltered, not normalized)
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Connectors and binectors
31
31
dec ... +(2
- 1) dec or
Normalization
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
∧ 100%
=
16384
Function
diag., Sheet
G120
G120
G120
G120
G120
G120
G120
G120
G120
G113
G113
G113
G113
G113
G113
G114
G114
G114
12-1