Siemens 6RA7086-6KS22 Operating Instructions Manual page 455

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

05.05
Fault
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
F056
Important parameter is not set
(active in operating states of ≤ o6)
This fault message is activated if certain parameters are still set to 0.
Fault value:
1
Speed controller actual value selection in P083 is still set to 0
2
Rated motor armature current in P100 is still set to 0.0
Rated motor field current in P102 is still set to 0.00 (fault message only when P082 ≠ 0)
3
4
Rated DC current of external field device is still set to 0.00 in U838 (error message if P082 >= 21 only)
F058
Parameter settings are not consistent
(active in operating states of ≤ o6)
Inconsistent values have been set in mutually dependent parameters.
Fault value:
2
The parameters for speed-dependent current limitation are not set correctly (the following applies: P105>P107 (I1>I2) and
P104 < P106 (n1<n2))
3
The field characteristic is not uniform
4
The first threshold for P gain adaptation of the speed controller set in parameter P556 is higher than the second threshold
setting in parameter P559
4
P557 is set to greater than P560
5
P558 is set to greater than P561
7
If P083=1 (analog tachometer), then P746 may not equal 0 (main actual value is not connected)
8
If P083=2 (pulse encoder), then P140 may not equal x0 (no pulse encoder installed)
9
If P083=3 (EMF control) then P082 may not equal x1x (field weakening operation)
10
P090 (stabilization time for supply voltage) >P086 (time for automatic restart)
11
P090 (stabilization time for supply voltage) >P089 (waiting time in state o4 or o5)
12
P445=1 is set (switch-on, shutdown and crawl act as a pushbutton) although no binector is parameterized as a shudown
button (P444=0)
13
If P067 > 1, then P075 must also be > 0
14
Parameter U673 > U674 (this setting is not permitted; see function diagram B152)
15
Parameter P169 = 1 and P170 = 1 (impermissible setting)
F059
Technology option S00 is disabled/will be disabled soon
(active in all operating statuses)
Fault value:
1
Time credit for S00 = 0 hrs
The technology option S00 for 500 operating hours no longer applies. The functions are now no longer available, but the
parameter settings have been retained.
If you wish to continue using technology option S00, please contact your nearest Siemens Sales Office to obtain the PIN
number you will require to permanently enable this option.
You will need to know the serial number of your SIMOREG DC Master. For further details, please refer to the description of
parameters U977 and n978 in Chapter 11 of the Parameter List.
2
Time credit S00 < 100 Std.
The remaining time period of temporary enabling of technology option S00 is now less than 100 operating hours. The
technology functions will not be available for much longer.
If you wish to continue using technology option S00, please contact your nearest Siemens Sales Office to obtain the PIN
number you will require to permanently enable this option.
for permanent enabling of technology option S00.
You will need to know the serial number of your SIMOREG DC Master. For further details, please refer to the description of
parameters U977 and n978 in Chapter 11 of the Parameter List.
3
S00 operation will not be possible if an SLB cycle time of < 1 ms is set
Owing to the available capacity of the electronics board, it is not possible to operate the S00 technology option at the same
time as a SIMOLINK bus with an extremely short cycle time (U746 < 1 ms).
See also parameter U746.
F060
Current total processor utilization (n009, K9990) > 100%
(active in all operating statuses)
The function blocks of the technology software, option S00 will not be calculated until this fault code has been acknowledged.
The current total processor utilization can be reduced by using the function U969 = 4.
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Description
Further information (r047.002 to r047.016)
Faults / Alarms
10-19