Start-Up
Recommended circuit for connecting SCB1 to SCI1 and SCI2 using fiber optic cables:
U425
X429
WARNING
If the 24 V voltage supply for an SCI slave fails which data are being exchanged between the
SCB1 and an SCI, then the "1" signal applied at a binary input is sent to the SCB1 or
SIMOREG as an "0" shortly before the power finally fails.
In contrast, the "1" remains applied in the SIMOREG in the event of an interruption in the fiber
optic connection.
If an external voltage (logical "1") has already been applied to a binary input when the electronics
supply voltage is switched on, this status will not be registered until the external voltage is
disconnected and reconnected again.
7.7.8.1

Diagnostic tools:

LED display on SCB1:
LED on
LED flashing
LED off
LED display on SCI1 or SCI2 slave:
LED on
LED flashing
LED off
Details about fault or alarm messages which may occur in relation to SCB1 or SCI (F070 to F079
and A049 and A050) can be found in Section 10.
7-56
SCB1
U121
U421
SCI1
X427
X428
Reset state
Normal operation
Error
Reset state
12Hz frequency No telegram traffic (e.g. fiber optic cable not
5Hz frequency
0.5Hz frequency Normal operation
Error
U125
U435
U431
SCI2
X439
X438
connected)
Faulty telegram traffic (e.g. fiber optic ring
interrupted or other slave has no supply
voltage)
X437
SIEMENS AG
SIMOREG DC Master
Operating Instructions
05.05
24V
6RX1700-0AD76