Parameter list
PNU
Description
P542
Time difference for dy/dt of ramp-function generator
Ramp-function generator:
FDS
Setting of dt for the output of dy/dt at a connector, i.e. at K0191, the change
in the output quantity of the ramp-function generator (K0190) is output within
(G136)
the period set in P542
Example: - The ramp-function generator is currently ramping up with a
ramp-up time of P311=5s, i.e. a ramp-up operation from y=0%
to y=100% takes 5s.
- A time difference dt of P542=2s is set.
- ⇒ A dy/dt of 40% appears at connector K0191 since the dy
within the set dt of 2 s equals (2s/5s)*100%..
(see also parameter P330)
P543
Threshold for SAD-dependent acceleration
With respect to the SAD-dependent acceleration function, only the
FDS
component of the speed controller setpoint/actual value difference which
has an absolute value in excess of the threshold set in this parameter is
(G153)
switched through (see also parameter P541).
Output (value to be multiplied by P541)
199.99%
negative
threshold
-200.00%
(-P543)
P546
Filter time for compensation of moment of inertia
FDS
(G153)
11-58
Input (setp./act. val. diff.)
positive
199.99%
threshold
(P543)
-200.00%
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
0.01 to 300.00
Ind: 4
[s]
FS=0.01
0.01s
Type: O2
0.00 to 100.00
Ind: 4
[%]
FS=0.00
0.01% of maximum
Type: O2
speed
0 to 10000
Ind: 4
[ms]
FS=0
1ms
Type: O2
SIEMENS AG
SIMOREG DC Master
Operating Instructions
05.05
See
Change
(Access /
Status)
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
6RX1700-0AD76