Parameter list
PNU
Description
Analog input terminals 10 / 11 (analog selectable input 3)
P731
Normalization of "Analog selectable input 3"
This parameter specifies the percentage value which is generated for an
FDS
input voltage of 10V (or an input current of 20mA) at the analog input.
(G114)
The following generally applies:
For voltage input:
[%] =
P
731
10
V
With current input:
[%] =
P
731
20
P732
Offset for "Analog selectable input 3"
(G114)
P733
Mode of signal injection at "Analog selectable input 3"
*
0 = Injection of signal with sign
1 = Injection of absolute value of signal
(G114)
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
P734
Source for selection of sign reversal at "Analog selectable input 3"
*
Selection of binector to control sign reversal at the analog input ("1" state
= reverse sign)
(G114)
0 = binector B0000
1 = binector B0001
etc.
P735
Filtering time for "Analog selectable input 3"
Note: Hardware filtering of approximately 1 ms is applied as standard.
(G114)
P736
Source for enabling of "Analog selectable input 3"
*
Selection of binector to control enabling of the analog input ("1" state =
enabled)
(G114)
0 = binector B0000
1 = binector B0001
etc.
Analog input terminals 103 / 104 (main actual value)
P741
Normalization for "Main actual value"
FDS
Rated value of input voltage at n max (=tachometer voltage at maximum
speed)
(G113)
This parameter defines the maximum speed when P083=1.
P742
Offset for "Main actual value" analog input
(G113)
P743
Mode of signal injection at "Main actual value" analog input
*
0 = Injection of signal with sign
1 = Injection of absolute value of signal
(G113)
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
P744
Source for selection of sign reversal at "Main actual value" analog
*
input
Selection of binector to control sign reversal at the analog input ("1" state
(G113)
= reverse sign)
0 = binector B0000
1 = binector B0001
etc.
11-78
Y
X .. Input voltage in volts
X
Y .. % value which is generated for input
voltage X
Y
X .. Input current in mA
mA
X
Y .. % value which is generated for input
current X
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
-1000.0 to 1000.0
Ind: 4
[%]
FS=100.0
0.1%
Type: I2
-200.00 to 199.99
Ind: None
[%]
FS=0.00
0.01%
Type: I2
0 to 3
Ind: None
1
FS=0
Type: O2
All binector numbers
Ind: None
1
FS=0
Type: L2
0 to 10000
Ind: None
[ms]
FS=0
1ms
Type: O2
All binector numbers
Ind: None
1
FS=1
Type: L2
-270.00 to 270.00
Ind: 4
[V]
FS=60.00
0.01V
Type: I2
-200.00 to 199.99
Ind: None
[%]
FS=0.00
0.01%
Type: I2
0 to 3
Ind: None
1
FS=0
Type: O2
All binector numbers
Ind: None
1
FS=0
Type: L2
SIEMENS AG
SIMOREG DC Master
Operating Instructions
05.05
See
Change
(Access /
Status)
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
6RX1700-0AD76