Parameter list
PNU
Description
Crawling setpoint
Function: Up to 8 connectors can be selected in P441 indices .01 to .08. These can be applied as an additional crawling setpoint (K0201,
K0206) via the binectors selected in P440, indices .01 to .08. P445 can be set to define whether the setpoint must be applied
when the selected binectors have reached the log. "1" state (when P445=0) or in response to a 0 → 1 transition (when
P445=1). When setpoint injection in response to a 0 → 1 transition is selected, the setpoint injection function is reset when the
binector selected in P444 switches to the log. "0" state. P442 indices .01 to .08 can be set to define for each setpoint
individually whether the ramp-function generator must be bypassed on setpoint injection.
If crawling setpoint injection is not selected, the connector set in P443 is applied to K0206.
P440
Source for injection of crawling setpoint
*
Selection of binector to control injection of the crawling setpoint.
(G130)
0 = binector B0000
1 = binector B0001
etc.
P441
Source for crawling setpoint
*
Selection of connector to be injected as the crawling setpoint
(G130)
0 = connector K0000
1 = connector K0001
etc.
P442
Source for selection of ramp-function generator bypass
*
Selection as to whether or not ramp-function generator must be bypassed
when the crawling setpoint is injected.
(G130)
The ramp-function generator is bypassed if the AND operation between the
binector selected via an index of P440 and the setting in the same index of
P442 produces a log. "1".
P443
Source for standard setpoint
*
Selection of the connector to be applied if crawling-setpoint injection is not
FDS
selected
0 = connector K0000
(G130)
1 = connector K0001
etc.
P444
Source for standstill command
*
Selection of the binector to control the standstill operation (OFF1) or
BDS
resetting of crawling setpoint injection when P445=1 (log. "0" state = reset).
0 = binector B0000
(G130)
1 = binector B0001
etc.
P445
Selection of level/edge for switch-on/crawling
*
Selection to define whether ON command must be input via terminal 37 and
the crawling setpoint injected in response to a log. "1" level or to a 0 → 1
(G130)
transition
0
ON with log. "1" state at terminal 37 and
injection of crawling setpoint with binectors selected in P440 in
log. "1" state
ON in response to 0 → 1 transition at terminal 37 and
1
injection of crawling setpoint in response to 0 → 1 transition of
binectors selected in P440
With this setting, the ON command or injection command for the
crawling setpoint is stored. The memory is reset when the
binector selected in P444 switches to the log. "0" state.
11-50
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
All binector numbers
Ind: 8
1
FS=0
Type: L2
All connector
Ind: 8
numbers
FS=0
1
Type: L2
0 to 1
Ind: 8
1
FS=0
Type: O2
All connector
Ind: 4
numbers
FS=207
1
Type: L2
All binector numbers
Ind: 2
1
FS=0
Type: L2
0 to 1
Ind: None
1
FS=0
Type: O2
SIEMENS AG
SIMOREG DC Master
Operating Instructions
05.05
See
Change
(Access /
Status)
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
6RX1700-0AD76