Siemens 6RA7086-6KS22 Operating Instructions Manual page 470

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

Parameter list
PNU
Description
o7
Waiting for switch-on command (=READY TO SWITCH ON)
o7.0
Waiting for switch-on command via terminal 37.
o7.1
Waiting for switch-on command via binector (acc. to selection in
P654) or control word, bit 0 (acc. to selection in P648).
o7.2
Waiting for cancellation of internal shutdown through input of an
internal shutdown command or
waiting for cancellation of command "Braking with field reversal"
o7.3
Waiting for completion of "Restore factory settings" operation.
o7.4
Waiting for switch-on command before execution of an
optimization run
o7.5
Wait for completion of "Read in parameter set" operation.
o7.6
Wait for completion of "Load MLFB" operation (performed at
factory)
o7.9
reserved for firmware download for optional supplementary
modules
o8
Waiting for acknowledgement of starting lockout
o8.0
Waiting for acknowledgement of starting lockout through input of
SHUTDOWN command (OFF1).
o8.1
Simulation operation active (see under U840) [SW1.7 and later]
o9
Fast stop (OFF3)
o9.0
Fast stop has been input via binector (acc. to selection in P658)
or control word, bit 2 (acc. to selection in P648).
o9.1
Fast stop has been input via binector (acc. to selection in P659).
o9.2
Fast stop has been input via binector (acc. to selection in P660).
o9.3
Fast stop is stored internally (memory can be reset by cancelling
FAST STOP command and entering SHUTDOWN).
o10
Voltage disconnection (OFF2)
o10.0
Voltage disconnection has been input via binector (acc. to
selection in P655) or control word, bit 1 (acc. to selection in
P648).
o10.1
Voltage disconnection has been input via binector (acc. to
selection in P656).
o10.2
Voltage disconnection has been input via binector (acc. to
selection in P657).
o10.3
E-Stop (safety shutdown) has been input via terminal 105 or 107
o10.4
Wait for receipt of a valid telegram on G-SST1 (only if telegram
failure time monitoring is set with P787 ≠ 0)
o10.5
Waiting for receipt of a valid telegram on G-SST2 (only if
telegram failure time monitoring is set with P797 ≠ 0)
o10.6
Waiting for receipt of a valid telegram on G-SST3 (only if
telegram failure time monitoring is set with P807 ≠ 0)
o11
Fault
o11.0
= Fxxx Fault message is displayed, red LED lights up.
o12
Electronics initialization in progress
o12.1
Basic converter electronics initialization in progress
o12.2
Supplementary board is sought in module plug-in location 2
o12.3
Supplementary board is sought in module plug-in location 3
o12.9
Restructuring of parameters in non-volatile storage after
software update (takes approx. 15s)
11-6
Value range
[Unit]
Steps
[SW 2.0 and later]
SIMOREG DC Master
05.05
No. indices
See
Factory
Change
setting
(Access /
Type
Status)