Siemens 6RA7086-6KS22 Operating Instructions Manual page 631

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

05.05
PNU
Description
U766
Normalization of analog outputs on EB1
(2766)
U
766
=
y
V [
]
x
100
%
x = normalization input (corresponds to filtering output)
(Z113)
y = normalization output (corresponds to output voltage at analog output
(Z116)
with an offset of 0)
i001: AO1 of the first EB1
i002: AO2 of the first EB1
i003: AO1 of the second EB1
i004: AO2 of the second EB1
U767
Offset for analog outputs on EB1
(2767)
i001: AO1 of the first EB1
i002: AO2 of the first EB1
(Z113)
i003: AO1 of the second EB1
(Z116)
i004: AO2 of the second EB1
n768
Display of analog outputs on EB1
(2768)
i001: AO1 of the first EB1
i002: AO2 of the first EB1
(Z113)
i003: AO1 of the second EB1
(Z116)
i004: AO2 of the second EB1
Source for output values at binary outputs on EB1 [SW 1.5 and later]
U769
(2769)
Selection of binectors to be applied to binary outputs at terminals 43 - 46.
*
0 = Binector B0000
1 = Binector B0001
etc.
(Z114)
(Z117)
i001: BO1 of the first EB1
i002: BO2 of the first EB1
i003: BO3 of the first EB1
i004: BO4 of the first EB1
i005: BO1 of the second EB1
i006: BO2 of the second EB1
i007: BO3 of the second EB1
i008: BO4 of the second EB1
n770
Display of status of binary inputs and outputs on EB1
(2770)
Representation on operator panel (PMU):
(Z114)
(Z117)
Segment ON:
Segment OFF:
Segment or bit
0 ....... Terminal 40
1 ....... Terminal 41
2 ....... Terminal 42
3 ....... Terminal 43
4 ....... Terminal 44
5 ....... Terminal 45
6 ....... Terminal 46
i001:
Terminal states of first EB1
i002:
Terminal states of second EB1
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
6
5
4
3
2
1
Corresponding terminal is activated
(HIGH level is applied)
Corresponding terminal is not activated
(LOW level is applied)
Value range
[Unit]
Steps
[SW 1.5 and later]
-200.00 to 199.99
[V]
0.01V
-10.00 to 10.00
[SW 1.5 and later]
[V]
0.01V
[SW 1.5 and later]
-200.0 to 199.99
[%]
0.01%
All binector numbers
1
[SW 1.5 and later]
0
Parameter list
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 4
P052 = 3
WE=10,00
P051 = 40
Typ: I2
on-line
Ind: 4
P052 = 3
WE=0,00
P051 = 40
Typ: I2
on-line
Ind: 4
P052 = 3
Typ: I2
Ind: 8
P052 = 3
WE=0
P051 = 40
Typ: L2
off-line
Ind: 2
P052 = 3
Typ: V2
11-167