Siemens 6RA7086-6KS22 Operating Instructions Manual page 185

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

05.05
Index
015/047 H byte: Mirroring of "DWord specifier act"
016/048 L byte: DPV1:DS_Write, pos. ack. counter
H byte: Reserved
017/049 L byte: DPV1:DS_Write, neg. ack. counter
H byte: Reserved
018/050 L byte: DPV1:DS_Read, pos. ack. counter
H byte: Reserved
019/051 L byte: DPV1:DS_Read, neg. ack. counter
H byte: Reserved
020/052 L byte: DP/T:GET DB99 pos. ack. counter
H byte: DP/T:PUT DB99 pos. ack. counter
021/053 L byte: DP/T:GET DB100 ps. ack. counter
H byte: DP/T:PUT DB100 ps. ack. counter
022/054 L byte: DP/T:GET DB101 ps. ack. counter
H byte: DP/T:PUT DB101 ps. ack. counter
023/055 L byte: DP/T service neg. acknow. counter
H byte: DP/T:Application association pos. acknow. counter
024/056 Reserved
025/057 Date of creation: Day, month
026/058 Date of creation: Year
027/059 Software version (Vx.yz, display x)
028/060 Software version (Vx.yz, display yz)
029/061 Software version: Flash-EPROM checks.
030/062 Reserved
031/063 Reserved
032/064 Reserved
Fault and alarm messages:
For details about fault messages, see Section 10.
Fault F080
An error occurred as board CBP2 was being initialized, e.g. incorrect value of a CB
parameter, incorrect bus address or defective module.
Fault F081
The heartbeat counter (counter on CBP2) which is monitored by SIMOREG for "signs of life"
from the board has not changed for at least 800 ms.
Fault F082
Failure of PZD telegrams or a fault in the transmission channel.
Alarm A081 (1
The identifier byte combinations transmitted by the DP master in the configuration telegram
do not match the permitted identifier byte combinations (configuring error on DP master)
Effect: No link can be established with the DP master, reconfiguration necessary.
Alarm A082 (1
No valid PPO type can be determined from the configuration telegram from the DP master.
Effect: No link can be established with the DP master, reconfiguration necessary.
Alarm A083 (1
No user data, or only invalid data, are being received from the DP master.
Effect: The process data are not transferred to the basic unit. When the telegram failure
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
st
CB) or alarm A089 (2
st
CB) or alarm A090 (2nd CB)
st
CB) or alarm A091 (2
Meaning for CBP2
nd
CB)
nd
CB)
Start-Up
7-27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents