ComAp IG-NT GC Reference Manual page 71

Inteli new technology modular generator controller multiple internal engines application – sw configuration spi
Hide thumbs Also See for IG-NT GC:
Table of Contents

Advertisement

ENABLED mode corresponds to the way that IG and IS controllers (previous generation) handled the
alarms.
ConvCoefPulse1 - 4
This setpoint adjusts the rate of increasing of the PulseCounter1 – 4 (integrating internal counters that can
be seen at PulseCounter1-4). The setpoint assigns number of pulses (BI:PulseCounter1 – 4) to increase the
PulseCounter integrating value by 1.
Step:
1/X
1 – 65000 1/X
Range:
Example:
Number of pulses on the physical input BI: PulseCounter1: 10
ConvCoefPulse1 = 2
Value of the PulseCounter1 integrating counter: 5
Inteli NT GeCon-MARINE SPI, SW Version 3.2, ©ComAp – July 2015
IGS-NT-GeCon-MARINE-SPI-3.2.PDF
[ ]
71