All protections are shown in Alarmlist and recorded into History, but the controller doesn't stop the engine
because of them. If the input is deactivated and some protections are still active or not yet reset, the
controller starts to take these protections into account and consequently stops the engine.
Take in account, that the binary outputs, signalizing activation of the particular protection are active
independently on the state of BI: SdOverride.
Hint:
nd
All 2
level protections are locked out, except of these:
Emergency stop
-
Binary and analog protections configured as Sd override type. In fact this protection type means:
-
"Unoverridable shutdown", i.e. it works the same way as standard shutdown protection, however it
can not be overriden (blocked) by the Sd override input.
Inteli NT GeCon-MARINE SPI, SW Version 3.2, ©ComAp – July 2015
IGS-NT-GeCon-MARINE-SPI-3.2.PDF
51
Need help?
Do you have a question about the IG-NT GC and is the answer not in the manual?
Questions and answers