Binary output: MCBButnEcho
Related FW
3.2
Description
This output provides 1s pulse when:
Binary output: GCB status
Related FW
3.2
Description
This output indicates the GCB position, how it is internally considered in the
controller. The position is based on
GCB fdb neg
The output can be used for indication of the GCB position.
Binary output: MCB status
Related FW
3.2
Description
This output indicates the MCB position, how it is internally considered in the
controller. The position is based on
MCB fdb neg
Inteli NT GeCon-MARINE SPI, SW Version 3.2, ©ComAp – July 2015
IGS-NT-GeCon-MARINE-SPI-3.2.PDF
GCB close/open command is received via communication line or
the input
GCBButton
MCB button is pressed on the controller front panel or
MCB button is pressed on any of external local/remote terminals or
MCB close/open command is received via communication line or
the input
MCBButton
input.
If only the positive feedback input is used the output mirrors the feedback.
If both feedbacks are used and they match each other the output
indicates the GCB position according to the feedbacks.
If both feedbacks are used, however they do not match each other, the
output remains in previous position when they matched.
input.
If only the positive feedback input is used the output mirrors the feedback.
If both feedbacks are used and they match each other the output
indicates the MCB position according to the feedbacks.
If both feedbacks are used, however they do not match each other, the
output remains in previous position when they matched.
is activated.
is activated.
GCB feedback
input and optionally also on the
MCB feedback
input and optionally also on the