deactivated. If the genset is running, the mode does not change until it is stopped.
Use this input if you need to disable the genset temporarily from any reason
(maintenance, control from a higher-level automation system etc..).
Binary input: Remote SEM
Related FW
3.2
Description
The controller is forced into SEM mode while this input is active.
N
OTE
Programming of firmware and/or configuration is disabled while this input is active,
as the programming is allowed in OFF mode only and GenConfig is not able to
switch the controller to OFF mode while SEM mode is forced by this input.
Binary input: Remote AUT
Related FW
3.2
Description
The controller is forced into AUT mode while this input is active.
N
OTE
Programming of firmware and/or configuration is disabled while this input is active,
as the programming is allowed in OFF mode only and GenConfig is not able to
switch the controller to OFF mode while AUT mode is forced by this input.
Binary input:Remote TEST
Related FW
3.2
Description
The controller is forced into TEST mode while this input is active. This input can
be used, among others, for following purposes:
Binary input: AccessLock int
Related FW
3.2
Description
This input forces the controller built-in terminal into monitoring mode.
N
OTE
As the IS-NT and IGS-NT-BB do not have built-in terminal, this input is assigned
to the terminal or IntelliVision (display) #1, which is supposed to be directly
attached to the controller or mounted close to it.
Inteli NT GeCon-MARINE SPI, SW Version 3.2, ©ComAp – July 2015
IGS-NT-GeCon-MARINE-SPI-3.2.PDF
:
:
In combination with a timer module for periodic testing of the engine.
In combination with the input
and take over the load by one binary signal (manual switch, higher-level
automation system etc.)
Setpoints changes are disabled.
Using control buttons on the panel is disabled even if the controller is in
MAN mode.
Change of controller mode is disabled.
:
Test on load
for forcing the genset to start
141