ComAp IG-NT GC Reference Manual page 117

Inteli new technology modular generator controller multiple internal engines application – sw configuration spi
Hide thumbs Also See for IG-NT GC:
Table of Contents

Advertisement

Value: Im3/EarthFC
Group
Mains values
Units
A
Related FW
3.2
Description
This value contains the current measured at the current input labeled "IN". This
input is used either for measurement of the mains current in phase L3 or for earth
fault current. The function depends on the setpoint
N
OTE
The ratio between the current measured at the input terminals and the displayed
current is adjusted by the setpoints
Value: P mains
Group
Mains values
Units
kW
Related FW
3.2
Description
Actual active power imported from the mains. Method of the mains import
measurement is adjusted by the setpoint
Value: Q mains
Group
Mains values
Units
kVAr
Related FW
3.2
Description
Actual reactive power imported from the mains. Method of the mains import
measurement is adjusted by the setpoint
Value: Mains PF
Group
Mains values
Units
-
Related FW
3.2
Description
Cos-phi factor at the mains inlet.
Value: Mains LChr
Group
Mains values
Units
-
Related FW
3.2
Description
Character of the load as it is seen from the mains side at the mains inlet. "L"
Inteli NT GeCon-MARINE SPI, SW Version 3.2, ©ComAp – July 2015
IGS-NT-GeCon-MARINE-SPI-3.2.PDF
:
I/E-Pm
meas.
Im3/ErFlCurCTp
and Im3/ErFlCurCTs.
I/E-Pm
meas.
I/E-Qm
meas.
117