Binary output: Ready for Load
Related FW
3.2
Description
This output is closed while the gen-set is running, it's voltage and frequency are in
limits and the GCB is able to be closed or is already closed.
Binary output: Gen-set active
Related FW
3.2
Description
The output closes at the beginning of the prestart phase and opens after the gen-
set has been fully stopped. If the gen-set fails to start the output opens after the
last cranking attempt.
N
OTE
The output also closes if the engine begins to rotate spontaneously.
Binary output: Operational
Related FW
3.2
Description
The output is closed when the gen-set is ready for operation or is currently in
operation.
Binary output: Not ready
Related FW
3.2
Description
The output is closed while the gen-set is not in operation, however it is not ready
to be put into operation. The output is closed while:
Binary output: Starting
Related FW
3.2
Description
The output is closed at the beginning of the prestart phase and remains closed
during prestart, cranking and starting phases. The output is opened either when
the gen-set goes to running phase or when it failed to start. See the diagram in the
descrition of the output
Binary output: Running
Related FW
3.2
Inteli NT GeCon-MARINE SPI, SW Version 3.2, ©ComAp – July 2015
IGS-NT-GeCon-MARINE-SPI-3.2.PDF
:
the genset is not running and
the controller is in OFF mode or
there is an alarm blocking start of the gen-set.
Cranking
for details.