Slip control adjusting:
10) Adjust Freq gain to unstable speed control and decrease value by 30 % to insure stable performance.
11) Adjust Freq int to stable (fast and smooth) slip control. Synchroscope movement on the controller
measure screen should slow down and stop (in any position, because Angle control is off).
Angle control adjusting:
12) Set Angle gain. Synchroscope on the controller measure screen should move slowly and stop in "up"
position. Set Angle gain to unstable value (synchroscope swings) and decrease value by 30 % to
insure stable performance.