ComAp IG-NT GC Reference Manual page 65

Inteli new technology modular generator controller multiple internal engines application – sw configuration spi
Hide thumbs Also See for IG-NT GC:
Table of Contents

Advertisement

The GCB can't be closed.
The message OfL StartBlck is present in the alarm list (see the alarm output
Synchro enable
Enable or disable forward/reverse synchronization.
NONE: No synchronizing is enabled.
FORWARD:
GCB synchronizing is enabled.
REVERSE:
MCB synchronizing is enabled.
BOTH: GCB and MCB synchronizing are enabled.
Force value possibility: Yes
MFStart enable
NO, YES:
Enables or disables automatic Mains failure start.
Force value possibility: Yes
Examples of settings:
MFStart
Parallel
ForwSync
enable
Enable
Enable
-
OFF
-
OFF
ON
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
ON
ON
ON
OFF
ON
ON
ON
Inteli NT GeCon-MARINE SPI, SW Version 3.2, ©ComAp – July 2015
IGS-NT-GeCon-MARINE-SPI-3.2.PDF
[ NONE / FORWARD / REVERSE / BOTH ]
[ NO / YES ]
RevSync
Island
Enable
enable
-
-
-
-
-
OFF
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
OFF
OFF
ON
OFF
ON
ON
ON
ON
ON
(FV)
Description
Not Ready - ParalDisabled
Gen-set starts after Rem start/stop is
closed, doesn't close GCB
Gen-set starts after Rem start/stop is
closed, synchronizes, closes GCB, at
Mains fail both MCB and GCB are opened
Gen-set starts after Rem start/stop is
closed, doesn't close GCB, if the Mains
fails, MCB is opened, gen-set keeps
running
Gen-set starts after Rem start/stop is
closed, GCB is not closed, if Mains fails,
MCB openes and GCB closes
Gen-set starts after Rem start/stop is
closed, synchronizes, closes GCB, if Mains
fails, opens MCB, stays in Island
Gen-set starts after Rem start/stop is
closed, synchronizes, closes GCB, if Mains
fails, MCB is opened, gen-set runs in
Island, reverse synchr., MCB closes
Gen-set starts after Mains fail, doesn't
close GCB - Island operation disabled
Gen-set starts after Mains fail, goes to
Island, if Mains returns, GCB is opened,
MCB is closed
Gen-set starts after Mains fail, opens MCB,
closes GCB, if Mains returns, opens GCB,
closes MCB, synchronizes GCB, closes
GCB
Gen-set starts after Mains fail, opens MCB,
closes
GCB,
if
the
synchronizes, closes MCB
Gen-set
starts
after
synchronizes, closes GCB, if Mains fails,
MCB is opened, gen-set runs in Island,
reverse synchr., MCB closes
OfL
StartBlck).
(FV)
Mains
returns,
Mains
fail,
65