ProcessControl:PeakAutS/S or ProcessControl:PeakKVAS/S del the gen-set is started (BO Sys start/stop
is
activated).
If
load
ProcessControl:PeakKVAStop
ProcessControl:PeakKVAS/S del the gen-set is stopped. Both Peak shaving based on kW and kVA can
work simultaneously (S
YS START
Apparent power is available in InteliGen-NT Basebox, InteliGen-NTC Basebox and InteliSys-NT only.
Figure: Example of peak shaving function based on Active power (the same function for Reactive power)
N
:
OTE
Function Peak Shaving based on Apparent power is not available for IG-NT-GC controller.
Remote Alarm Messaging
It is possible to use up to five channels for Active Call, Email and SMS upon defined type of Alarm. It is
possible to define protection type for all ENABLED channels to react. All the possibilities in the controller are:
History record, Alarm only, Warning, Mains protect and Mains protect with Reset. Find more information
about alarm types in the chapter Protections and alarm management.
Communication Types for Remote Alarm Messaging
Below there all types of communication available for each Active Call channel.
DATA-ANA: This option sends a complete archive to the recipient's PC via analog modem. An analog
modem must be connected either to one of controller COM ports or to one of I-LB modules connected to the
controller via CAN2 bus. The channel address must contain complete telephone number of the recipient's
PC where InteliMonitor is running in Active call receiving mode.
DATA-GSM: This option sends a complete archive to the recipient's PC via GSM modem. A GSM modem
with activated CSD data transfers must be connected either to one of controller COM ports or to one of I-LB
modules connected to the controller via CAN2 bus. The channel address must contain complete telephone
number of the recipient's PC where InteliMonitor is running in Active call receiving mode.
DATA-ISDN: This option sends a complete archive to the recipient's PC via ISDN modem. An ISDN modem
must be connected either to one of controller COM ports or to one of I-LB modules connected to the
controller via CAN2 bus. The channel address must contain complete telephone number of the recipient's
PC where InteliMonitor is running in Active call receiving mode.
DATA-CDMA: This option sends a complete archive to the recipient's PC via CDMA modem. A CDMA
modem must be connected either to one of controller COM ports or to one of I-LB modules connected to the
controller via CAN2 bus. The local CDMA network must allow point-to-point data transfers. The channel
address must contain complete telephone number of the recipient's PC where InteliMonitor is running in
Active call receiving mode.
SMS-GSM: This option sends a short text message (SMS) containing the actual Alarmlist contents to the
recipient's mobile phone via the GSM modem. The channel address must contain complete telephone
number of the recipient's mobile phone.
SMS-CDMA: This option sends a short text message (SMS) containing the actual Alarmlist contents to the
recipient's mobile phone via the CDMA modem. The channel address must contain complete telephone
number of the recipient's mobile phone.
Inteli NT GeCon-MARINE SPI, SW Version 3.2, ©ComAp – July 2015
IGS-NT-GeCon-MARINE-SPI-3.2.PDF
consumption
decreases
for
period
/
is activated if at least one condition is fulfilled). Peak shaving based on
STOP
PeakLevelStart
PeakLevelStop
Sys start/stop
below
ProcessControl:PeakLevelStop
longer
than
ProcessControl:PeakAutS/S del
PeakAutS/S del
Time
PeakAutS/S del
or
or
30