FltRes GoToSEM
DISABLED: Controller stays in AUT mode after Fault reset .
ENABLED: Automatic switch from AUT to SEM mode after Fault reset to avoid automatic engine start. This
function is active for all 2
Force value:
Yes
Hint:
Set to ENABLED to avoid automatic engine start when Fault reset button is pressed after shut down in
automatic mode.
Local buttons
PANEL:
Only the buttons on the controller front panel are enabled.
EXTBUTTONS: Only the external signals (copies of the panel buttons) are enabled.
BOTH:
Both controller buttons and external signals are enabled.
Hint:
This switch is valid for these signals: GCBButton, MCBButton, FaultResButton, HornResButton, StartButton,
StopButton.
DispBaklightTO
Range [units] OFF, 1-240 min, NO TIMEOUT [min]
This setpoint adjusts timeout after which the display (internal display or IS display #1) backlight is switched
off.
N
:
OTE
When IntelliVision is used this setpoint does not adjust its behavior. Its backlight is adjusted by internal
IntelliVision "setpoint".
OFF
NO TIMEOUT
DispBlkStrtOff
Range [units] DISABLED, ENABLED [-]
If this setpoint is in ENABLED position the display backlight is temporarily switched off during gen-set start.
UserBtn pulse
[s ] (FV)
Step:
0,1 [ s ]
0,2 ...10 s
Range:
Force value:
Yes
Setpoint UserBtn pulse allows user to choose the duration of UserButton pulse.
ResetActAlarms
DISABLED:
If Fault reset is activated (from any source), only inactive (normally displayed) alarms are
reset. So only inactive alarms can be cleared from the Alarmlist.
ENABLED:
If Fault reset is activated (from any source), all currently present (including inverse displayed
= active) alarms are reset (asterisk in Alarmlist disappears for all present alarms). I.e. after an active (inverse
displayed) alarm later on becomes inactive (normally displayed), it is cleared automatically from the Alarmlist
if previously reset.
Hint:
Inteli NT GeCon-MARINE SPI, SW Version 3.2, ©ComAp – July 2015
IGS-NT-GeCon-MARINE-SPI-3.2.PDF
[ DISABLED / ENABLED ]
nd
-level protections (Shut down, Slow stop, ElProt, Off-load).
[ PANEL / EXTBUTTONS / BOTH ]
The backlight is off all the time
The backlight is on all the time
[- ] (FV)
[ DISABLED / ENABLED ]
(FV)
[min]
(FV)
70