ComAp IG-NT GC Reference Manual page 105

Inteli new technology modular generator controller multiple internal engines application – sw configuration spi
Hide thumbs Also See for IG-NT GC:
Table of Contents

Advertisement

ShutdownOvr
Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when a Shutdown
Override type protection occurs.
Force value:
Yes
AcallCH1..3-Type
Up to three separate channels are available for any of the following types of messages:
DISABLED:
Channel is disabled.
DATA-ANA:
Standard analog modem connection to monitoring SW.
DATA-GSM:
Standard GSM modem connection to monitoring SW.
DATA-ISDN:
Standard ISDN modem connection to monitoring SW.
DATA-CDMA:
CDMA modem connection to monitoring SW.
SMS-GSM:
Channel sends SMS message via GSM network. Only with GSM modem connected.
SMS-CDMA:
Channel sends SMS message via CDMA network. Only with CDMA modem connected.
IB-E-MAIL:
Channel sends E-mail. Only when IG-IB connected.
IB-EML-SMS:
Channel sends E-mail in short format (SMS). Only when IG-IB connected.
An Email contains
header with serial number and application info
-
Alarm list contents
-
latest 20 History records (reason, date, time)
-
Example of EML-SMS:
AL=(Sd Water Temp,Wrn Water Temp,!Emerg Stop,ActCallCH1Fail)
Hint:
GSM modem must be connected to controller for Active GSM call or SMS.
IG-IB does not support direct SMS, just as an email.
Connected device type (Analog / GSM / ISDN / CDMA modem) is recognized automatically.
AcallCH1..3-Addr
Address for channel 1...3 active call. Each above message type has either a phone number or an e-mail
address associated to it.
For more details see PC software guide chapter IG-IB Internet communication.
Hint:
To receive active call run InteliMonitor – Type of connection = Active call. Active call window contains list of
received ANT files. Each list item contains Gen-set name, Date, Time, controller serial number.
NumberRings AA
Number of rings prior to answering the modem connection from PC to controller.
Step:
1 – 30
Range:
Hint:
NumberRings AA change is not accepted immediately but after controller is switched on or when modem is
connected to controller.
ActCallAttempt
When an active call is issued, this setpoint defines the number of attempts to deliver the message.
Step:
1
Range:
1 to 250
Hint:
Timeout for connection is 90 sec and after 120 sec controller starts the next attempt. During the time the
controller is trying to issue an active call, incoming calls are blocked.
Inteli NT GeCon-MARINE SPI, SW Version 3.2, ©ComAp – July 2015
IGS-NT-GeCon-MARINE-SPI-3.2.PDF
[DISABLED / ENABLED ]
(FV)
[ ]
1
[ 1 to 250 ]
(FV)
105