ComAp IG-NT GC Reference Manual page 124

Inteli new technology modular generator controller multiple internal engines application – sw configuration spi
Hide thumbs Also See for IG-NT GC:
Table of Contents

Advertisement

Description
Temperature inside the controller (on the CPU).
Value: D+
Group
Analog CU
Units
V
Related FW
3.2
Description
Voltage measured at the D+ terminal. If this voltage is > 80% of the
terminal is evaluated as active and the engine is evaluated as running. See also
the chapter
Value: AIN input 1
Group
Analog CU
Units
configurable
Related FW
3.2
Description
This is the value of the analog input 1 of the controller. Analog inputs are fully
configurable so the name and units depend on configuration. In the default
configuration the input is used for oil pressure measurement.
Value: AIN input 2
Group
Analog CU
Units
configurable
Related FW
3.2
Description
This is the value of the analog input 2 of the controller. Analog inputs are fully
configurable so the name and units depend on configuration. In the default
configuration the input is used for water temperature measurement.
Value: AIN input 3
Group
Analog CU
Units
configurable
Related FW
3.2
Description
This is the value of the analog input 3 of the controller. Analog inputs are fully
configurable so the name and units depend on configuration. In the default
configuration the input is used for fuel level measurement.
Value: AIN input 4
Group
Analog CU
Units
configurable
Related FW
3.2
Description
This is the value of the analog input 4 of the controller. Analog inputs are fully
configurable so the name and units depend on configuration. In the default
Inteli NT GeCon-MARINE SPI, SW Version 3.2, ©ComAp – July 2015
IGS-NT-GeCon-MARINE-SPI-3.2.PDF
Start
sequence.
Ubat
the D+
124

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IG-NT GC and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Is-ntc-bbIg-ntc gcIs-ntIg-nt-bbIg-ntc-bb

Table of Contents