Description
Temperature inside the controller (on the CPU).
Value: D+
Group
Analog CU
Units
V
Related FW
3.2
Description
Voltage measured at the D+ terminal. If this voltage is > 80% of the
terminal is evaluated as active and the engine is evaluated as running. See also
the chapter
Value: AIN input 1
Group
Analog CU
Units
configurable
Related FW
3.2
Description
This is the value of the analog input 1 of the controller. Analog inputs are fully
configurable so the name and units depend on configuration. In the default
configuration the input is used for oil pressure measurement.
Value: AIN input 2
Group
Analog CU
Units
configurable
Related FW
3.2
Description
This is the value of the analog input 2 of the controller. Analog inputs are fully
configurable so the name and units depend on configuration. In the default
configuration the input is used for water temperature measurement.
Value: AIN input 3
Group
Analog CU
Units
configurable
Related FW
3.2
Description
This is the value of the analog input 3 of the controller. Analog inputs are fully
configurable so the name and units depend on configuration. In the default
configuration the input is used for fuel level measurement.
Value: AIN input 4
Group
Analog CU
Units
configurable
Related FW
3.2
Description
This is the value of the analog input 4 of the controller. Analog inputs are fully
configurable so the name and units depend on configuration. In the default