evaluate GCBCloseEna signal.
Binary input: New Alarm
Related FW
3.2
Description
This LBO generates one pulse (length 1s) when new alarm is added to alarm list.
Binary input: New ECU Alarm
Related FW
3.2
Description
This LBO generates one pulse (lenth 1s) when new alarm from ECU is added to
alarm list.
Binary output: ModbusSw1-32
Related FW
3.2
Description
These LBO show state of Modbus switches (registers) 1-32.
The modbus registers are shown in the controller in the form of two values and
also as a set of logical binary outputs. These outputs may be used further in the
configuration and connected to other functions in the controller.
Binary output: Initialized
Related FW
3.2
Description
This logical binary output function can be used for indication of fully initialized
controller after power on. Furthermore it is useful to block Delay functions in the
controller during the initialization phase of controller power up (outputs of Delays
in the controller are activated immediately during the power on if Delay input is
active prior and during the power up).
Inteli NT GeCon-MARINE SPI, SW Version 3.2, ©ComAp – July 2015
IGS-NT-GeCon-MARINE-SPI-3.2.PDF
GCB on Button
+
BO: GCBCloseEna
GCB on pulse
221

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IG-NT GC and is the answer not in the manual?

This manual is also suitable for:

Is-ntc-bbIg-ntc gcIs-ntIg-nt-bbIg-ntc-bb

Table of Contents

Save PDF