Select the proper function
Show = appears when LBI gets active
Hide = disappears when LBI gets active
None = no function
Select the object
Select which User Mask is used for
this object
N
:
OTE
Masking of screens in InteliVision 5 supports only Show function
Use also other masking functions (masking can react on several internal states, e.g. activation of Timers).
Remote Control Function
It is possible to remotely control several Binary Outputs in the controller. You can either use Remote
Switches tool in InteliMonitor (select Remote switches in menu for corresponding controller), import Remote
Switches tool to a SCADA diagram in Line Diagram Editor or use external device via Modbus (register
#46361 and command #26 (1A hex), for more information on Modbus please refer to the InteliGen/InteliSys
Communication guide).
Remote Switch will activate or deactivate depending on remote control so it can be used to manually control
devices, simulate malfunctions while commissioning etc.
Figure: Remote Switches tool in InteliMonitor, Remote Switches tools in Line Diagram Editor and Mobus commands
Inteli NT GeCon-MARINE SPI, SW Version 3.2, ©ComAp – July 2015