Response: "AVal7 -30.2222"
Caution!
Query-response sequences are not synchronized. E.g. zone status messages could be output
!
between query and response, see following example.
Consequences
Example of unsynchronized output:
AVal 7?
Id3.4 ON P12 Z3,Z5-12,Z15 AVal7 -30.2222
FAULT REPORTING
The ASCII Control Protocol can be used to report faults to external systems. The set of error types to be output via the
ASCII Control Protocol can be configured at the Supervision dialog of the Controller.
Following format is used to report faults: Fault <Id>#<Parameter> <State> "<Text>"
Element
Description
Id
Stable fault number of fault IDs, see table below.
Parameter
Stable fault parameter of error value, see table below.
State
0 if fault disappeared, 1 if fault occurred
Text
User defined error message including the variable %u substituted with a parameter value

PVA-4R24

The PVA-4R24 24 Zone Router is a zone extension for the PAVIRO system. The PVA-4R24 adds 24 zones, 20 GPIs, 24
GPOs and 2 control relays to the system and is controlled and supervised via the CAN bus by the PVA-4CR12
(Controller). Up to 20 external routers can be connected to one controller. One router can handle up to 4000 W
speaker load. The maximum load of one zone is 500 W.
The zone indicator lights on the front indicate the current status of every zone:
Green: Zone in use for non emergency purpose
Red: Zone in use for emergency purpose
Yellow: Zone fault detected
Off: Zone in idle condition
PVA-4R24 Device
Start by creating a PVA-4R24 Device in your IRIS-Net project. Drag a PVA-4R24 from the Object Bar's Devices category
or from the Devices window into the worksheet (see also chapters: Devices and Configurations menu). The following
dialog box appears:
Bosch Security Systems B.V.
User Manual
PAVIRO | en
965