For assigning a Boolean value via the ASCII Control Protocol the Task Engine block type „Input Logic" is used. The
value of the block's property function must be set to <LVal><id>. The value of the block's property connection must be
set to PMX-4CR12_x.OpenInterface
Analog values
Following format is used to edit the value of a analog value: <AVal><id> <value>
Element
Description
AVal
Indicates the use of a analog value in the Task Engine
id
Unique identifier of the analog value in the Task Engine
value
Rational number to be assigned to the analog value
Example:
AVal7 -30.222
For assigning a rational number via the ASCII Control Protocol the Task Engine block type „Input Analog" is used. The
value of the block's property function must be set to <AVal><id>.
OUTPUT VIA THE ASCII CONTROL PROTOCOL
The ASCII Control Protocol allows to query values (rational numbers or Boolean values) of the Controller's Task Engine.
Logic values
Following format is used to query the value of a logic value: <LVal><id> ?
Element
Description
LVal
Indicates the use of a logic value in the Task Engine
id
Unique identifier of the logic value in the Task Engine
?
Question mark
Example:
Query: "LVal 7?"
Reponse: "LVal7 1"
Analog values
Following format is used to query the value of a analog value: <AVal><id> ?
Element
Description
AVal
Indicates the use of a analog value in the Task Engine
id
Unique identifier of the analog value in the Task Engine
?
Question mark
Example:
Query: "AVal 7"
Response: "AVal7 -30.2222"