4.2.14
Connecting to CV500/CV1000/CV2000 or CVM1
■1. Setting DIP switches
Set the DIP switches.
(1) Host link RS-422/232 switch
For RS-232 communication
(2) DIP switches
Switch No.
6
5
4
3
2
1
PERIPHERAL
HOST LINK
RS-232
M/C
ON
RS-422
DIP switch
(inside battery compartment)
RS-232
RS-422
RS-232 (up)
For RS-232
communication
OFF (no terminating resistor)
Settings
For RS-422 communication
RS-422 (down)
Settings
ON (terminating resistor attached)
OFF
OFF
OFF
OFF
OFF
4.2 Serial Connection
For RS-422
communication
4 - 37
4