■2. GOT Ethernet Common Setting
Set the following setting which is common to the standard port and the extension port, or port 1 and port 2.
Step 1.
Select [System] → [GOT Setup] → [GOT Ethernet Setting] → [GOT Ethernet Base Setting] from the menu.
Step 2.
Set the followings.
Item
Default Gateway
Peripheral S/W Communication Port No.
Transparent Port No.
■3. IP Filter Setting
Step 1.
Select [System] → [GOT Setup] → [GOT Ethernet Setting] → [IP Filter Setting] from the menu.
Step 2.
For the detailed settings, refer to the following manual.
GT Designer3 (GOT2000) Screen Design Manual
Description
Set the router address of the default gateway where the GOT is
connected.
(Only for connection via router)
(Default: 0.0.0.0)
Set the GOT port No. for the communication with the peripheral S/W.
(Default: 5015)
Set the GOT port No. for the transparent function.
(Default: 5014)
1.1 Setting the Communication Interface
Range
0.0.0.0 to 255.255.255.255
1024 to 65534 (Except for 5011
to 5013, 49153 to 49170)
1024 to 65534 (Except for 5011
to 5013, 49153 to 49170)
1 - 15
1