(13) RS485 connection diagram 13)
GOT side
SDA
1
SDB
6
RDA
2
RDB
7
SG
5
RSA
3
CSA
4
RSB
8
CSB
9
*1
Pin No. of controller differs depending on the model. Refer to the following table.
*2
Terminating resistor should be provided for a controller which will be terminating resistors.
*3
Set the terminating resistor of The GOT side.
➠ ■3.
*4
Do not connect SG of the controller and SG of the GOT.
■2. Precautions when preparing a cable
(1) Cable length
The maximum length of the RS-485 cable must be 1,200m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
(3) CHINO controller side connector
Use the connector compatible with the CHINO controller side module.
For details, refer to the user's manual of the CHINO controller.
■3. Connecting terminating resistors
(1) GOT side
(a)
For GT27, GT25(Except GT2505-V), GT23
Set the terminating resistor setting switch of the GOT main unit to "Enable".
(b)
For GT2505-V
Set the terminating resistor selector to "110Ω".
1.4.3 Terminating resistors of GOT
(2) CHINO controller side
When connecting a CHINO controller to the GOT, a terminating resistor must be connected to the CHINO controller.
User's Manual of the CHINO controller
*3
Controller
RDA
RDB
SDA
SDB
*4
SG
Connecting terminating resistors
Signal name
RDA
RDB
SDA
SDB
SG
Terminating resistor(100Ω 1/4W)
*1
Controller
RDA
RDB
SDA
SDB
SG
Controller type
SE3000
JU
Terminal name
Terminal No.
RDA
3
RDB
4
SDA
1
SDB
2
SG
5
11.3 Connection Diagram
* 2
*1
KE3000
LE5000
Terminal name
Terminal name
RDA
RDA
RDB
RDB
SDA
SDA
SDB
SDB
SG
SG