11.5.4

Connecting to DB1000, DB2000 Series

■1. Communication settings
Set the communication settings with controller key operation.
Protocol
Function
*1
Station No.
*2
Transmission speed
Character
*1
*2
11.5.5
Connecting to GT120 Series
■1. Key Lock setting
To write the Digital and the Analog parameters, set the Key Lock setting to Lock 3.
■2. Communication settings
Release the controller lock function in advance and set the following communication settings.
After completing the communication settings, set the Key Lock setting to Lock 3.
Communication protocol
*1
Station No.
*2
Transmission speed
Data bit
*2
Stop bit
*2
Parity bit
*1
*2
11 - 28
11.5 Controller Side Setting
Item
Avoid duplication of the station No. with any of the other units.
Adjust the settings with GOT settings.
Item
Avoid duplication of the station No. with any of the other units.
Adjust the settings with GOT settings.
Set value
MODBUS (RTU)
Com: Upper communication
01 to 99
9600bps, 19200bps, 38400bps
7BIT/EVEN/STOP1
7BIT/EVEN/STOP2
7BIT/ODD/STOP1
7BIT/ODD/STOP2
8BIT/NON/STOP1
8BIT/NON/STOP2
8BIT/EVEN/STOP1
8BIT/EVEN/STOP2
8BIT/ODD/STOP1
8BIT/ODD/STOP2
Set value
comr: MODBUS RTU
1 to 95
96: 9600bps
192: 19200bps
8bits (fixed)
1bit, 2bits
nonE: None
EVEn: Even
odd: Odd