(2) EtherNet/IP (OMRON NJ), Gateway
Make the settings according to the usage environment.
Item
GOT Net No.
*1
GOT Station
GOT Communication Port No.
*3
Startup Time
*2
Timeout Time
Delay Time
*1
Each of [GOT Station] set in the communication detail setting and [Station] set in the Ethernet setting must be set to different
station numbers.
➠ ■4.
*2
When [CJ1W-EIP21] is set for [Controller Type] in [Ethernet], even if [Timeout Time] is set to 10 seconds or shorter, the GOT
operates with timeout time of 10 seconds.
In the above setting, when [CJ1W-EIP21] and [OMRON NJ] are mixed in [Controller Type] for [Ethernet], for [OMRON NJ] (built-
in port connecting side), the GOT operates with timeout time of 10 seconds.
➠ ■4.
*3
When writing or reading OMRON NJ tag immediately after NJ series setup, a system alarm may occur.
In this case, make the time to start communication with NJ series longer in [Startup Time].
For details, refer to the following manual.
■3. GOT Ethernet Setting
The GOT can be connected to a different network by configuring the following setting.
(1) GOT IP address setting
Set the following communication port setting.
• Standard port (When using GT25-W, port 1)
• Extension port (When using GT25-W, port 2)
(2) GOT Ethernet common setting
Set the following setting which is common to the standard port and the extension port, or port 1 and port 2.
• [Default Gateway]
• [Peripheral S/W Communication Port No.]
• [Transparent Port No.]
(3) IP filter setting
By configuring the IP filter setting, the access from the specific IP address can be permitted or shut off.
For the detailed settings, refer to the following manual.
1.1.2 GOT Ethernet Setting
Set the network No. of the GOT.
(Default: 1)
Set the station No. of the GOT.
(Default: 18)
Set the GOT port No. for the connection with the Ethernet
module.
(Default: 5034)
Specify the time period from the GOT startup until GOT starts
the communication with the PLC CPU. (Default: 3sec)
Set the time period for a communication to time out. (Default:
3sec)
Set the delay time for reducing the load of the network/
destination PLC. (Default: 0ms)
Ethernet setting
Ethernet setting
GT Designer3 (GOT2000) Screen Design Manual
Description
4.3 Ethernet Connection
Range
1 to 239
1 to 64
1024 to 5010, 5014 to 65534
(Except for 5011, 5012, 5013
and 49153 to 49170)
3 to 255sec
1 to 90sec
0 to 10000
( 10ms)
4 - 53
4