Mitsubishi Electric GOT2000 Series Connection Manual page 182

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(26) RS485 connection diagram 26)
GOT side
SDA
SDB
RDA
RDB
SG
RSA
RSB
CSA
CSB
*1
Signal name
*2
*3
*4
*5
■2. Precautions when preparing a cable
(1) Cable length
The length of the RS-485 cable must be 500m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
(3) AZBIL control equipment side connector
Use the connector compatible with the AZBIL control equipment side module.
For details, refer to the user's manual of the AZBIL control equipment.
■3. Connecting terminating resistors
(1) GOT side
Set the terminating resistor by operating the terminating resistor setting switch.
For the procedure to set the terminating resistor, refer to the following.
(2) AZBIL control equipment side
When connecting a AZBIL control equipment to the GOT, a terminating resistor must be connected.
3 - 56
3.3 Connection Diagram
Terminating resistor (150Ω 1/2W)
*4
* 3
* 5
* 5
* 5
* 5
Pin No. of control equipment differs depending on the model. Refer to the following table.
SDC45/46
Pin No.
DA
C10
DB
C11
SG
C12
Terminating resistor should be provided for an Interface converter and a control equipment which will be terminals.
Connect FG grounding to the single-sided end of a cable shield line.
Set the terminating resistor of GOT as follows.
Set the terminating resistor setting switch of the GOT main unit to "110Ω".
➠ ■3.
Connecting terminating resistors
The signals RSA, RSB, CSA, and CSB are not provided for
1.4.1 GOT connector specifications
1.4.3 Terminating resistors of GOT
3.5 Control Equipment Side Setting
*2
Control equipment side
* 1
DA
DB
SG
* 3
Model of control equipment
CMS
MQV
CMF015
MPC
Pin No.
Pin No.
5
7
6
8
10
9
. Return connection is not required.
Control equipment side
* 1
DA
DB
SG
MVF
RX
Pin No.
Pin No.
1
1
2
2
7
3