(26) RS485 connection diagram 26)
GOT side
SDA
SDB
RDA
RDB
SG
RSA
RSB
CSA
CSB
*1
Signal name
*2
*3
*4
*5
■2. Precautions when preparing a cable
(1) Cable length
The length of the RS-485 cable must be 500m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
➠
(3) AZBIL control equipment side connector
Use the connector compatible with the AZBIL control equipment side module.
For details, refer to the user's manual of the AZBIL control equipment.
■3. Connecting terminating resistors
(1) GOT side
Set the terminating resistor by operating the terminating resistor setting switch.
For the procedure to set the terminating resistor, refer to the following.
➠
(2) AZBIL control equipment side
When connecting a AZBIL control equipment to the GOT, a terminating resistor must be connected.
➠
3 - 56
3.3 Connection Diagram
Terminating resistor (150Ω 1/2W)
*4
* 3
* 5
* 5
* 5
* 5
Pin No. of control equipment differs depending on the model. Refer to the following table.
SDC45/46
Pin No.
DA
C10
DB
C11
SG
C12
Terminating resistor should be provided for an Interface converter and a control equipment which will be terminals.
Connect FG grounding to the single-sided end of a cable shield line.
Set the terminating resistor of GOT as follows.
Set the terminating resistor setting switch of the GOT main unit to "110Ω".
➠ ■3.
Connecting terminating resistors
The signals RSA, RSB, CSA, and CSB are not provided for
1.4.1 GOT connector specifications
1.4.3 Terminating resistors of GOT
3.5 Control Equipment Side Setting
*2
Control equipment side
* 1
DA
DB
SG
* 3
Model of control equipment
CMS
MQV
CMF015
MPC
Pin No.
Pin No.
5
7
6
8
10
9
. Return connection is not required.
Control equipment side
* 1
DA
DB
SG
MVF
RX
Pin No.
Pin No.
1
1
2
2
7
3