■2. When connecting to multiple PLCs
D2-240
D2-DCM
D2-250-1
D2-260
PLC
Data
communications
Model name
*1
module
D2-250-1
D2-260
-
(communication
port 2)
D2-240
D2-250-1
D2-DCM
D2-260
*1
*2
*3
7 - 14
7.2 System Configuration
D2-240
D2-250-1
D2-260
Cable model
Communication
Connection diagram
Type
RS-422
connection diagram 8)
RS-422
connection diagram 7)
The data communications module is manufactured by KOYO ELECTRONICS INDUSTRIES CO., LTD.
For details of the product, contact KOYO ELECTRONICS INDUSTRIES CO., LTD.
When the number of links exceeds 30, use a transmission line conversion unit D-01CV per 30 links.
For details, refer to the following manual.
KOYO EI PLC user's Manual
GT25-W, GT2505-V does not support the option device.
D2-DCM
Connection cable
Connection cable
Max.
Option device
distance
number
- (Built into GOT)
RS-422
1000m
- (Built into GOT)
RS-422
1200m
GOT
GOT
*3
Model
GT15-RS4-9S
GT15-RS4-9S
Communication driver
KOYO KOSTAC/DL
Number of
connectable
equipment
90 PLCs for
*2
1 GOT
90 data
communication
*2
module for 1 GOT