Emergency-stop and protective door monitoring
Table of Contents

Advertisement

1 Description ESR5-NO-31-24VDC

1.9 Function description

9
Dual-channel sensor circuit
The dual-channel sensor circuit is connected the same as for cross-fault
detection.
→ Section 3.4.3, "Terminal models Signal encoder", page27
Automatic start
The device will start automatically after the sensor circuit is closed.
→ Section 3.4.4, "Connection options Start and feedback circuit", page27
→ Section 1.10, "Function and time diagrams", page10
Safe shut-down
When the sensor circuit is opened, enable current paths S13/14, 23/24, and
33/34 will be opened without delay.
When the enable current paths are open, the device will be in a safe state.
The signal current path closes.