Wiring a Remote Reset Switch (Optional)

The main WPC processor board has two terminals for wiring a remote reset switch. The
remote reset terminal can be wired to the equipment that you choose, or you can just use a
simple switch to activate the circuit. Connect a wire from terminal #70 on the main
processor board to a normally open switch. Connect another wire from the switch to ground.
WPC is reset with a momentary connection to ground.

Wiring Operator Mode Outputs (Optional)

SmartPAC with WPC provides outputs to customer-supplied solid-state relays to monitor
WPC's operator mode. As an example, the following schematic illustrates how to monitor
when WPC is in Automatic Single Stroke.
WARNING
These operator mode outputs are
NOT control reliable. They can,
however, be used as a convenience to
interface automation.
Pin #
Pin Designation
118
+13.5 VDC (Power)
117
Ground
116
+5 VDC
115
(Unused)
114
ON in Continuous (2-Hand or Foot)
113
ON in Automatic Single Stroke
112
ON in Foot Single Stroke
111
ON in One-Hand Single Stroke
110
ON in Two-Hand Single Stroke
109
ON in Inch Mode (1-Hand or 2 Hand)
108
(Unused)
Example showing wiring
for a relay to turn on when
Automatic Single Stroke
mode is selected.
Figure 2 - 11. One Way to Wire WPC Operator Mode Outputs
Page 56
SmartPAC 2 with WPC Integration
J506
DISPLAY
BOARD
CONNECTOR
Chapter 2
Installing SmartPAC 2 and WPC
TB501
SERIAL COMM.
CONNECTOR
TB502
OPERATOR
MODE
OUTPUT
CONNECTOR
OPERATOR MODE
OUTPUTS CAN
SWITCH 8 MA OF
DC CURRENT TO
GROUND; MAX
VOLTAGE 24 VDC