Section 4
Binary input and output modules
4.1.3.1
Table 19:
BIM Non group settings (basic)
Name
Operation
DebounceTime
OscBlock
OscRelease
4.1.3.2
Table 20:
IOMIN Non group settings (basic)
Name
Operation
DebounceTime
OscBlock
OscRelease
60
Setting parameters for binary input modules
Values (Range)
Unit
Off
-
On
0.001 - 0.020
s
1 - 40
Hz
1 - 30
Hz
Setting parameters for binary input/output module
Values (Range)
Unit
Off
-
On
0.001 - 0.020
s
1 - 40
Hz
1 - 30
Hz
Step
Default
-
On
0.001
0.001
1
40
1
30
Step
Default
-
On
0.001
0.001
1
40
1
30
1MRK 505 394-UEN A
Description
Operation Off/On
Debounce time for binary inputs
Oscillation block limit
Oscillation release limit
Description
Binary input/output module in operation
(On) or not (Off)
Debounce time for binary inputs
Oscillation block limit
Oscillation release limit
Line differential protection RED650 2.2 IEC
Technical manual
PID-3473-SETTINGS v2
PID-4050-SETTINGS v2