Setting Parameters For Binary Input Modules; Setting Parameters For Binary Input/Output Module - ABB REL650 Technical Manual

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Section 4
Binary input and output modules
4.1.3.1
Table 19:
BIM Non group settings (basic)
Name
Operation
DebounceTime
OscBlock
OscRelease
4.1.3.2
Table 20:
IOMIN Non group settings (basic)
Name
Operation
DebounceTime
OscBlock
OscRelease
62

Setting parameters for binary input modules

Values (Range)
Unit
Off
-
On
0.001 - 0.020
s
1 - 40
Hz
1 - 30
Hz

Setting parameters for binary input/output module

Values (Range)
Unit
Off
-
On
0.001 - 0.020
s
1 - 40
Hz
1 - 30
Hz
Step
Default
-
On
0.001
0.001
1
40
1
30
Step
Default
-
On
0.001
0.001
1
40
1
30
1MRK 506 382-UEN A
Description
Operation Off/On
Debounce time for binary inputs
Oscillation block limit
Oscillation release limit
Description
Binary input/output module in operation
(On) or not (Off)
Debounce time for binary inputs
Oscillation block limit
Oscillation release limit
Line distance protection REL650 2.2 IEC
Technical manual
PID-3473-SETTINGS v2
PID-4050-SETTINGS v2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 650 series

Table of Contents