VISTA-128B Installation and Setup Guide
One class B/style B EOLR-supervised auxiliary input zone.
Operating power and communication with control panels via the V-Plex polling loop.
Electronics mounted in a small plastic case with tamper-protected cover.
Powerline Carrier Devices
Powerline Carrier devices are controlled by signals sent through the electrical wiring at the
premises via a 4300 transformer. Therefore, if using Powerline Carrier devices, a 4300
transformer must be used in place of the regular system transformer.
This section is used to program relays to activate in response to a programmed condition. The
system can also be programmed to activate relays at specific times by using the #80 Scheduling
Menu Mode–Time Driven Events function.

Installing the 4204 and 4204CF Relay Modules

The relay module will not operate until the device address you have set the DIP switches for is
enabled in the control's Device Programming in the #93 Menu Mode .
To wire the relay modules, perform the following steps:
Step
1
2
3
9-2
Action
Set the 4204 or 4204CF's DIP switches for a device address between 01-15. See
Figures 9-1 and 9-2.
Make sure the address is not being used by another device (keypads, RF
receivers, etc.).
Mount the 4204 and 4204CF Modules as per the instructions provided with the
modules.
Connect the module's wire harness to the keypad terminals (6, 7, 8, and 9). Plug
the connector at the other end of the harness into the module.
If mounted remotely homerun each module to the control. The table
below shows the maximum wire run lengths from the control to each
4204. Refer to the instructions provided with the 4204CF for its
maximum permissible wire lengths.
Wire Gauge
Maximum Length
#22
#20
#18
#16
125 feet
200 feet
300 feet
500 feet