Table of Contents Zone Number Designations ..........................4-4 Zone Response Type Definitions........................4-5 Zone Input Type Definitions ..........................4-7 Programming the Control for the Pager......................4-8 Programming for Access Control........................4-8 Programming for ECP Long Range Radio .....................4-10 Programming for the Event Log........................4-10 SECTION 5: Data Field Descriptions ....................5-1 About Data Field Programming ........................5-1 Programming Data Fields ..........................5-1 SECTION 6: Scheduling Options .....................
Page 5
California State Fire Marshal (CSFM) Requirements..................A-2 APPENDIX B: Summary of System Commands................B-1 APPENDIX C: Specifications......................C-1 APPENDIX D: Contact ID Event Codes....................D-1 TABLE OF CONTACT ID EVENT CODES ..................... D-1 Index ............................Index-1 THE LIMITATIONS OF THIS ALARM SYSTEM ADEMCO LIMITED WARRANTY...
List of Figures x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x Figure 3-1: Installing the Lock...............................3-1 Figure 3-2: Cabinet Attack Resistance Considerations ......................3-2 Figure 3-3: Mounting the PC Board............................3-2...
1 = YES 0 = NO 0 ✴ Additional system options are programmed via data fields, which are indicated by a “star” ( followed by the data field number. PRODUCT MODEL NUMBERS: Unless noted otherwise, references to specific model numbers represent ADEMCO products.
Page 8
VISTA-32FB/VISTA-128FB Installation and Setup Guide viii...
The VISTA-32FB/VISTA-128FB can interface with the following devices: An ECP Long Range Radio that can send Contact ID messages An access control system by using either the ADEMCO PassPoint system (via the VISTA Gateway Module) or a VistaKey module (via the polling loop)
Page 10
#70 Relay Command Mode. Supports additional style-Y supervised Notification Appliance Circuits using a 4204CF. Supports the ADEMCO 4285/4286 VIP Module, which allows access to the system from either a remote location or on the premises The 4285/4286 VIP Module is not Listed for use with the VISTA-32FB/VISTA-128FB Control Panel in a UL installation.
Page 11
128 zones, as well as openings and closings for all 150 users. This requires central stations to be equipped with the ADEMCO 685 receiver using software level 4.10 or higher to fully support all new VISTA-32FB/VISTA-128FB report codes. If you need to update your 685 receiver, contact your distributor.
Page 12
VISTA-32FB/VISTA-128FB Installation and Setup Guide...
S E C T I O N Partitioning x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x Theory of Partitioning This system provides the ability to arm and disarm up to 8 different areas (2 in the VISTA-32FB), as if each had its own control.
Page 14
VISTA-32FB/VISTA-128FB Installation and Setup Guide The Common Lobby feature employs logic for automatic arming and disarming of the common lobby. Two programming fields determine the way the common lobby will react relative to the status of other partitions. They are: 1*18 Affects Lobby and 1*19 Arms Lobby.
Section 2 – Partitioning Sequence #2: Office 1 Office 2 Lobby Action User #2: (Armed) Disarms Disarms User #1: Disarms (Disarmed) (No change) (Disarmed) Arms No Change User #2: User #1: Arms (Armed) No Change Notice that in sequence #1, because Office #2 was the last to arm, the lobby also armed (Office #2 is programmed to affect and arm the lobby).
Page 16
VISTA-32FB/VISTA-128FB Installation and Setup Guide The following is a typical display: S Y S T E M 1 2 3 4 5 6 7 8 S T A T U S R R N N A Possible status indications include: A = Armed Away S = Armed Stay M = Armed Maximum...
BOTTOM it is held securely by its snap tabs. Figure 3-1: Installing the Lock Use an Ademco No. K4445 Lock (supplied). Grade A Mercantile Premises Listing Guidelines The panel door must be supervised. Mount the All wiring between the bell and panel must be run clip-on tamper switch (supplied) to the cabinet's in conduit.
VISTA-32FB/VISTA-128FB Installation and Setup Guide (Shows typical local Grade A listing installation) RUN BELL WIRES IN CONDUIT PLUG THIS KNOCKOUT TO PLUG AN UNUSED KNOCKOUT OPENING, REMOVE KNOCKOUT AND INSTALL A PAIR OF CLIP-ON DOOR DISC PLUGS AND A CARRIAGE BOLT AS SHOWN. TAMPER SWITCH DISC PLUGS (DIMPLES IN DISC CABINET...
When the control’s auxiliary power load for all devices exceeds 1A, you can power additional keypads from a Connect keypad(s) to terminals 11, 12, 13, regulated 12VDC power supply (e.g., ADEMCO and 14 on the control board, see Figure 3-4. AD12612 (1.2A)). Use a UL Listed, battery-backed NOTE: If using only one keypad, it may be supply for UL installations.
Compatible Alarm Indicating Devices Selectable for supervision. Model Device Type Selectable to activate by individual zone assignments ADEMCO AB12 Grade A Bell System Sensor PA400B Indoor piezo sounder Selectable for confirmation of arming ding. (beige/PA400R (red) rated at 90dB @ 10 feet.
BELL 1 FACTORY DEFAULTS BELL 1 IS CONFIGURED AS A BURGLARY BELL CIRCUIT USE NONPOLARIZED GRADE A INDICATING DEVICES (e.g., ADEMCO NO AB12 - SEE WIRING NOTES BELOW) WIRING IS NOT SUPERVISED; CUT WHITE JUMPER, W1, BELL 1 BELL 2 ON MAIN PCB.
VISTA-32FB/VISTA-128FB Installation and Setup Guide If field 3 61 = 4, the auxiliary relay remains activated When field 3 61 = 1, the auxiliary relay can be ✳ ✳ until User Code + # + 67 is entered. This option can be programmed to give a brief activation for confirmation of arming ding (field 3 57) or Chime Mode (field 3...
4.10 or higher. If you need to update your 685 Receiver, contact your distributor. Installing the 5140DLM Backup Dialer The system supports ADEMCO Low Speed 3+1; 4+1; 4+2; Sescoa/Radionics 3+1; 4+1; 4+2; ADEMCO 4+2 Do not connect the main dialer and the backup Express;...
VISTA-32FB/VISTA-128FB Installation and Setup Guide Wiring Burglary and Panic Devices to Zones 1-8 The maximum zone resistance is 100 ohms for Wiring 2-Wire Smoke Detectors to Zones 1 and 2 zones 1, 2 and 8, and 300 ohms for all other zones (excluding the 2K EOL resistor).
Section 3 - Installing the Control To wire 4-wire smoke detectors to zones 1-8, perform Wiring 4-Wire Smoke Detectors the following steps: Power to 4-wire smoke detectors must be Step Action supervised with an EOL device (use a System Sensor A77-716B EOL relay module connected Select 4-wire smoke detectors (see list of as shown in Figure 3-10 ).
32FB/VISTA-128FB Cabinet Door Tamper Switch and audible alarm (zone type 7) when more than one for the ADEMCO AB12 Grade A Burglary Bell Box burglary partition is used. Enable the Zone 6 Alternate Tamper Switches and Tamper Liner. The bell Housing’s Tamper Function (program field 3 ✳...
Section 3 - Installing the Control Using 2-Wire Latching Glassbreaks on Zone 8 The alarm current provided by zone 8 supports only one glassbreak detector in Zone 8 can support 2-wire glassbreak detectors. The the alarmed state. zone provides enough standby current to power up to 50 Do not use other N.O.
VISTA-32FB/VISTA-128FB Installation and Setup Guide Compatible Polling Loop Devices Step Action Wire each device to the polling loop, making Model Type sure of the correct polarity (refer to the Number device’s instructions). 4208 8-Zone Expander NOTE: If you are using serial number 4190WH 2-Zone Expander devices, and intend to enroll each device...
Section 3 - Installing the Control Be sure to include the total current drawn on DO NOT use the 4197 Polling Loop Extender the polling loop when figuring the total auxiliary module with the VISTA-32FB/VISTA-128FB . load on the panel’s power supply. INPUT POLLING LOOP EXTENSION POLLING LOOP 4297...
VISTA-32FB/VISTA-128FB Installation and Setup Guide Using two receivers does not increase the RF System Operation and Supervision number of transmitters the system can support The 5800 RF system operation has the following (127 zones using the 5881H, plus a wireless characteristics: keypad).
Section 3 - Installing the Control ANTENNAS TO CONTROL'S REMOTE KEYPAD CONNECTION POINTS. EACH RECEIVER MUST BE ON INDIVIDUAL HOME RUN. INSERT IN USE MAX. of 220 ft. [67m of #22 (0.64mm) CIRCUIT RIGHT-HAND WIRE or 550 ft. (168m) of #18 (1mm) WIRE BOARD TERMINALS FOR EACH RUN.
Page 32
VISTA-32FB/VISTA-128FB Installation and Setup Guide Transmitter Battery Life The 5808 smoke detector can be programmed Batteries in the wireless transmitters may last from 4 as a “Smart Contact” in Zone Progamming . to 7 years, depending on the environment, usage, and This enables the detector to monitor the specific wireless device being used.
Electronics mounted in a small plastic case with tamper-protected cover. Installing a Remote Keyswitch A UL-Listed remote keyswitch, such as the ADEMCO In UL commercial fire installations, mount the 4146, can be used for remote arming/disarming of the keyswitch next to the keypad. The keypad burglary part of the system and for silencing alarms.
SWITCH (N.O.) the associated partition is disarmed. TO ZONE 7 + (TERM 25) Wiring for the Remote Keyswitch 2000 OHMS To install the ADEMCO 4146 keyswitch, perform the EOLR following steps: 4146 KEYSWITCH Figure 3-22: Remote Keyswitch Wiring Step Action Connect the ADEMCO 4146 to the panel as shown in Figure 3-22.
VISTA-32FB/VISTA-128FB Installation and Setup Guide Installing a Remote Keypad Sounder An optional Amseco PAL 328N Piezo Sounder can be J2 CONNECTOR used to duplicate the sounds produced by the keypad’s built-in sounder. The remote sounder will duplicate all sounds (such as alarms, trouble beeps, etc.) except for the short beeps associated with keypad key depression.
These triggers may be used to trip auxiliary alarm The fire and burglary/audible panic alarm triggers are signaling equipment such as ADEMCO’s 7720, normally LOW and go HIGH until a User Code + OFF 7720ULF, and 7920SE Long Range Radios.
VISTA-32FB/VISTA-128FB Installation and Setup Guide Installing the 4100APG Pager Interface Whenever an event occurs on the VISTA-32FB/VISTA- Mounting the 4100APG 128FB, a message can be sent to a pager. This is The 4100APG may be mounted in the control cabinet if accomplished by using the 4100APG Pager Interface.
Section 3 - Installing the Control Violet 11 12 4100SM Aux. Pwr Aux. Gnd Black DB-25 4100APG DB-9 Serial Port Input RJ-11 Line To Telco Figure 3-26: Wiring the 4100APG Without the Serial Printer Wiring the 4100APG With the Event Log Printer The VISTA-32FB/VISTA-128FB will support the The serial printer must be configured for 1200 4100APG and serial printer.
VISTA-32FB/VISTA-128FB Installation and Setup Guide Access Control Using VistaKey The VistaKey is a single-door access control module. Mounting and Wiring the VistaKey When connected to the VISTA-32FB/VISTA-128FB, it provides access control to the protected premises. The For detailed instructions on how to install and alarm system supports up to 8 VistaKey modules (8 program the VistaKey, refer the Installation and access points) (4 modules supported on VISTA-32FB).
Section 3 - Installing the Control 14V MAX (12V @ 85-160mA Nominal) POLLING LOOP + TO ALARM SYSTEM CONTROL PANEL POLLING LOOP - POLLING LOOP TERMINALS. THIS DEVICE COMPLIES WITH PART 15 CLASS A ZONE A (DSM) LIMITS OF FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: ZONE B (RTE) (1) IT MAY NOT CAUSE HARMFUL INTERFERENCE.
VISTA-32FB/VISTA-128FB Installation and Setup Guide Event Log Connections This system has the ability to record up to 512 events of various categories in the Event Log (history log). Each J2 CONNECTOR event is recorded with the time and date of its occurrence (if real-time clock is set).
Page 43
Section 3 - Installing the Control The 4285/4286 is wired between the control panel and Step Action the premises’ handset(s) (see Figure 3-31). It listens for TouchTones on the phone line and reports them to the Connect the module to the phone line as control panel.
VISTA-32FB/VISTA-128FB Installation and Setup Guide SPEAKER NOTE: IF CONNECTING SINGLE SPEAKER, USE 8-ohm INCOMING TELCO LINE SPEAKER ONLY. IF CONNECTING 2 SPEAKERS, USE 4-ohm OR 8-ohm SPEAKERS AND CONNECT IN SERIES. MAIN RJ31X CALLER DIALER JACK JACK ID UNIT JACK CONTROL PANEL 8-CONDUCTOR DOUBLE PLUG CORD...
Section 3 - Installing the Control PREMISES ANSWERING ANSWERING ALL SWITCHES OFF MACHINE AND PHONES MACHINE EXCEPT SWITCH 5 (WHICH SHOULD BE ON) INCOMING TELCO LINE REFER TO AAV MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS CALLER RJ31X AND MICROPHONE ID UNIT JACK CONTROL...
VISTA-32FB/VISTA-128FB Installation and Setup Guide Earth Ground Connections In order for the lightning transient protective devices in To connect the earth ground, perform the following this product to be effective, the designated earth ground steps: terminal (terminal 30) must be terminated in a good Step Action earth ground.
Page 47
Section 3 - Installing the Control In Worksheet 1, enter devices used on the polling In Worksheet 3, enter devices used on Auxiliary loop. Calculate total current draw on the polling Power 2. Calculate standby and alarm currents, loop. then add to get Auxiliary Power 2 current subtotal. Worksheet 1: Total Polling Loop Current Draw Worksheet 3: Auxiliary Power 2 Current Load Polling Loop Device...
VISTA-32FB/VISTA-128FB Installation and Setup Guide In Worksheet 5, enter devices connected to the Bell In Worksheet 6, enter the total calculated subtotals 2 Output. Calculate alarm currents, then add to get of all listed outputs from Worksheets 1 through 5, the Bell 2 Output current subtotal.
Section 3 - Installing the Control Using the total calculated from Worksheet 6, Connect the battery, referring to Figure 3-33. calculate the battery capacity required for the installation. The standby battery is automatically tested for 10 minutes every 4 hours, beginning 4 hours Worksheet 7: Battery Capacity Calculation Worksheet after exiting Programming mode.
Page 50
VISTA-32FB/VISTA-128FB Installation and Setup Guide 3-34...
S E C T I O N Programming x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x NOTE: All references in this manual for number of zones, user codes, partitions, VistaKey modules, the master partition and the event log capacity, use the VISTA-128FB’s features.
VISTA-32FB/VISTA-128FB Installation and Setup Guide NOTE: If the number of digits that you enter in a data Entry Errors field is fewer than the maximum permitted (for If an address is improperly entered, the keypad example, a phone number), the keypad displays the last displays “FC.”...
Section 4 – Programming Below are the main menu selections. For details refer to the VISTA-32FB/VISTA-128FB Programming Guide. MAIN MENU OPTIONS For programming the following: ZONE PROG? Zone Number 1 = YES 0 = NO Zone Response Type Partition Number for Zone Dialer report code for zone Input Device Type for zone (whether RF, polling loop, etc.) Enrolling serial numbers of 5800 Series transmitters &...
VISTA-32FB/VISTA-128FB Installation and Setup Guide Following is a list of commands used while in the Menu Mode: #93 Menu Mode Programming Commands Enters Menu Mode. Serves as [ENTER] key. Press to have keypad accept entry. [✳] Backs up to previous screen. Press to answer NO.
Page 56
VISTA-32FB/VISTA-128FB Installation and Setup Guide Type 02: Entry/Exit #2 Burglary Type 08: 24-Hour Auxiliary Alarm Provides a secondary entry delay, if the system is Sends a report to central station and provides an alarm armed in the AWAY or STAY modes and the zone is sound at the keypad only.
Section 4 – Programming Type 21: Arm-AWAY (5800 Series devices only) Type 28: Main Logic Board (MLB) Supervision Causes the system to arm in the AWAY mode when the Used to supervise the MLB. If communication between zone is activated. the MLB and the VISTA Gateway Module (VGM) fails, a trouble condition is annunciated for the zone.
VISTA-32FB/VISTA-128FB Installation and Setup Guide Programming the Control for the Pager In field *64 enter 1 to enable the 4100APG pager In field *72 enter the Pager ID number of the interface. paging service for Open/Close reports. This is the PIN number.
Page 59
Section 4 – Programming Access Control of an Entry/Exit Point Using VistaKey Using Wireless Keypads Wireless keypads (5827 & 5827BD) can provide another or PassPoint The control can send entry and exit requests to the way of entering or exiting the premises. They function VistaKey or PassPoint ACS utilizing keypads and the same as alpha keypads, except when the code + # 73 button-type (BR) RF transmitters.
VISTA-32FB/VISTA-128FB Installation and Setup Guide Programming for ECP Long Range Radio Program the LRR in Device Programming in the Program field ✳58: Selects events for the primary #93 Menu Mode Programming. sub’s ID Program field ✳56: Selects the time the panel Program field ✳59: Selects events for the secondary should wait before it attempts to send a message to sub’s ID.
S E C T I O N Data Field Descriptions x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x About Data Field Programming The following pages list this control’s data fields in numerical order.
Page 62
VISTA-32FB/VISTA-128FB Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION % % 15 The keyswitch requires the use of zone 7 wired loop (zone 7 is no longer Keyswitch Assignment available as protection zone). The fire and panic alarm voltage triggers (J2) Enter 1-8 partition keyswitch is being used.
If you select TouchTone, make sure the subscriber has requested and is paying for TouchTone service. Note that whether or not TouchTone dialing for call placement is permitted, communication by the use of DTMF signaling (ADEMCO High Speed) will still take place. See field 1*33 for TouchTone w/Rotary backup % % 31...
Must be 00 for UL commercial fire and burglary installations. % % 45 Enter the reporting format for the primary telephone number. Primary Format 0=Low Speed; 1=Contact ID; 2=ADEMCO High Speed; 3=ADEMCO Express % % 46 Enter the low speed format for the primary telephone number.
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION % % 49 If enabled, the system for either or both primary/secondary formats sends a Checksum Verification verification digit to validate the message at the receiver without having to send Enter 2 digits, one for the primary and one two message rounds.
VISTA-32FB/VISTA-128FB Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION % % 67 Enter the paging service phone number for Trouble reports. Enter up to 17 Pager Phone Number for digits. Do not fill unused spaces. Supervision Enter 0-9; #11 for *, #12 for #, #13 for a 2- second pause.
The rest of the system is armed. Also, the following dialer reports are sent to the central station if programmed: Exit Error by User (not sent when is using ADEMCO High Speed format); Entry/Exit or Interior Alarm with the zone number; Bypass reports.
Page 68
VISTA-32FB/VISTA-128FB Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION 1 % % 21 If enabled, when the panel is armed, the normal exit delay begins. After the Exit Delay Reset user exits, closes the door and then re-enters the premises, the exit delay 0 = disable time is reset to the programmed value.
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION 1 % % 26 Select for the A, B, and C keys whether the system performs a panic or a Panic Button or Speedkey speedkey function when the key is pressed. For A, B, C keys: Select for the D key whether the system performs a specific macro or if the 00 = panic function...
Page 70
VISTA-32FB/VISTA-128FB Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION 1 % % 42 If enabled, the system defeats Call Waiting on the first outgoing call attempt to Call Waiting Defeat both the primary and secondary numbers. 0 = disable NOTES: 1 = enable After the panel's initial call to report the alarm, the panel may attempt to make...
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION 1 % % 58 If enabled, allows the RF button user to force a bypass of all faulted zones Enable 5800 RF Button Force when arming the system. NOTE: When attempting to arm the system, the keypad beeps once after the 0 = disable button is pressed if any faulted zones are present.
Page 72
VISTA-32FB/VISTA-128FB Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION 2 % % 05 This is the time between the end of the arming window and the start of auto- Auto-Arm Delay (partition- arm warning time (field 2*06). specific) 00 = no delay.
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION 2 % % 21 There are three entries in this field as follows: Fire, Burglary/Audible Panic, Supervision Pulses for LRR Silent Panic/Duress. 0 = disable If enabled, causes the control to send periodic short pulses on the J2 radio 1 = enable triggers to the LRR.
Page 74
VISTA-32FB/VISTA-128FB Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION 3 % % 18 ✳ This option allows the delay programmed in field 3 16 for Waterflow and Extended Delay for Zone Types Supervisory zones to be extended by 4 times. 17 &...
Page 75
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION 3 % % 57 This field has two entries, one for bell 2 and one for the auxiliary relay. If Confirmation of Arming Ding Bell enabled, produces ½-second external alarm sounding (“ding”) at the end of 2 &...
Page 76
VISTA-32FB/VISTA-128FB Installation and Setup Guide 5-16...
S E C T I O N Scheduling Options x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x You must program Bypass and Auto-Arm Fail reports for UL installations.
VISTA-32FB/VISTA-128FB Installation and Setup Guide Exception Reports Time-Driven Events This option allows the reporting of openings and The system can automatically activate and de-activate closings to the central station only if the arming and relays at predetermined times to turn lights or other disarming occurs outside of the predetermined opening devices on and off.
Section 6 – Scheduling Options Open/Close Schedules Definitions General Additional Schedules The open/close scheduling is controlled by one of three Additional opening and closing schedules can be schedules. Each schedule consists of one time window programmed using the Time-Driven Event for openings and one time window for closings.
VISTA-32FB/VISTA-128FB Installation and Setup Guide Scheduling Menu Mode The #80 Scheduling Menu Mode is used to program Steps to Program Scheduling Options most of the scheduling and timed-event options. Enter User Code + [#] + [8] + [0] from the normal operating This section contains examples of the mode.
Section 6 – Scheduling Options PROMPT EXPLANATION Enter 1 to program holiday schedules. Refer to Holiday Schedule Programming later in this section for Holidays ? detailed procedures. 1 = YES 0 = NO Enter 0 to move to the “Timed Events?” prompt. Enter 1 to program timed events for relay outputs, additional schedules, and other system functions.
VISTA-32FB/VISTA-128FB Installation and Setup Guide Daily Open/Close Schedules Each partition can be assigned one daily open/close Open/Close Schedule Worksheet schedule, plus a holiday schedule. Temporary The following worksheet is an example of the worksheet schedules are programmed separately, using the #81 found in the Programming Guide.
Section 6 – Scheduling Options Holiday Schedule Worksheet The following worksheet is an example of the worksheet found in the Programming Guide. Partition Month/Day 3…16 Holiday Schedule Programming After entering Scheduling Menu Mode, press [0] until the “Holidays ?” prompt appears. PROMPT EXPLANATION Enter 1 to program holiday schedules.
Page 84
VISTA-32FB/VISTA-128FB Installation and Setup Guide Enter the code for the desired action and Open/Close Windows action specifier. The action codes represent the events that are to take place when the scheduled Action Code Action Action Specifier time is reached. Each action also requires an Enable Opening Window by Partition(s) action specifier, which defines what the action will...
Page 85
Section 6 – Scheduling Options Enter the desired activation time (when the Time-Driven Event Programming action is to take place). Select from: The following menu items must first be programmed in Output Programming in the #93 Menu Mode: Activation Description Time Enter Relay No.
Page 86
VISTA-32FB/VISTA-128FB Installation and Setup Guide ACTION CODES EXPLANATION ACTION SPECIFIER 30=Auto bypass – Zone list Actions 30-31 01 ZONE LIST ? 31=Auto unbypass – Zone list If you selected actions 30-31, the prompt at the right appears. Enter the zone ENTER 01-15 list number that contains the zones to be bypassed or unbypassed.
Section 6 – Scheduling Options PROMPT EXPLANATION Enter the activation time from 1-10 (listed below). As the number is keyed in, the activation time is 01 Active time ? displayed. The choices are: 1: Trigger at the start of the window. 2: Trigger at the end of the window.
VISTA-32FB/VISTA-128FB Installation and Setup Guide PROMPT EXPLANATION Enter the second time-window number from 01-20 for this access schedule for the displayed day. As the MON A1 Window 2 ? number is keyed in, the actual time that has been stored for the window is displayed. 00:00 00:00 Press [✳] to continue.
Page 89
Section 6 – Scheduling Options Temporary Schedules Programming Enter User Code + [#] + 81 to enter this mode. PROMPT EXPLANATION This prompt is for entering the start and end times of the disarm (opening) window for Monday. Mon DISARM WIND. Upon entry of this mode, the cursor is positioned on the tens of hours digit of the start time of the disarm 00:00AM 00:00AM window.
Page 90
VISTA-32FB/VISTA-128FB Installation and Setup Guide PROMPT EXPLANATION Enter the desired output number (01-96). As the number is entered, the descriptor for that output device is 06 ENTER OUTPUT# displayed. PORCH LITE Press [✳] to continue. Entering 00 as the output number deletes the timer (Timer 06, in this example) and displays an output descriptor of “None.”...
COMPASS DOWNLOADING software available on CD ROM with a complete User’s Manual. It may NOTES: also be downloaded from the ADEMCO web page. Each time the control panel is accessed The web address is http://www.ademco.com. successfully, a Callback Requested report is sent to the central station, if Opening reports are programmed.
VISTA-32FB/VISTA-128FB Installation and Setup Guide Getting On-Line with a Control Panel At the protected premises, the control panel must be To download a control without programming any connected to the existing telephone line (refer to the information, perform the following steps: SECTION 3: Installing the Control).
Section 24 - Downloading Primer Direct-Wire Downloading The VISTA-32FB/VISTA-128FB can be downloaded Connector J2 on the main PC board (see the Summary without using a modem or telephone line by using a of Connections diagram on the inside back cover of this 4100SM Serial Module and Compass Downloading manual) is intended to be interfaced to either a local Software.
Page 94
VISTA-32FB/VISTA-128FB Installation and Setup Guide...
S E C T I O N Setting the Real-Time Clock x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x General Information This system provides a real-time clock, which must be set in order for the system’s event log to keep track of...
Page 96
VISTA-32FB/VISTA-128FB Installation and Setup Guide...
S E C T I O N User Access Codes x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x General Information The VISTA-32FB system allows a total of 75 security access codes to be allocated.
Temporary codes are entered as 4-digit numbers. ADEMCO Contact ID format is capable of reporting Users 001-150 uniquely. If any other report format is used, only user numbers 001 – 015 can uniquely report to the central station.
Section 9 – User Access Codes Adding a Master, Manager, or Operator Code Enter Installer Code † + [8] + new user no. (002-150) During user code entry, normal key depressions at other keypads in a partition are + new user’s code ignored.
VISTA-32FB/VISTA-128FB Installation and Setup Guide Changing a Master, Manager, or Operator Code Enter Installer Code * + [8] + new user no. (002-150) + new user’s code * Or Master or Manager Code, but the code must be a higher level of authority than the code being changed (e.g. a Manager Code can add an Operator-level Code, but cannot add a Master or another Manager Code).
S E C T I O N Testing the System x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x Battery Test When AC power is present, the VISTA-32FB/VISTA- If the VISTA-32FB/VISTA-128FB finds that the battery...
VISTA-32FB/VISTA-128FB Installation and Setup Guide PROMPT EXPLANATION Enter 1 (YES) to have the system automatically test all polling loop points with a fire response type 9 or 16. AUTO-TEST DET? Other fire zones will have to be tested manually. 0=NO 1=YES Enter 0 (NO) to test every point manually.
Section 10 – Testing The System Armed Burglary System Test x Alarm messages are sent to the central Step Action station during the armed tests. Notify the Check the keypad-initiated alarms, if central station that a test will be in progress. programmed, by pressing the panic key pairs x A display of “COMM FAILURE”...
VISTA-32FB/VISTA-128FB Installation and Setup Guide Trouble Conditions Supervisory Messages Other System Messages Display Description Display Description SUPV + This indicates that a fire supervisory COMM Indicates a failure occurred in the condition exists on the zone number telephone communication portion of your Zone FAILURE displayed.
A P P E N D I X Regulatory Agency Statements x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x UL Installation Requirements The following requirements apply to both UL residential and UL commercial burglary installations: 1.
VISTA-32FB/VISTA-128FB Installation and Setup Guide 4. Wire an ADEMCO AB12 Grade A Bell/Box to the Notification Appliance Circuit. Bell wires must be run in conduit. Program the Notification Appliance Circuit for 16 minutes or longer timeout and for confirmation of arming ding. (Also see SECTION 3: Installing the Control) 5.
Page 109
Appendix A – Regulatory Agency Statements FEDERAL COMMUNICATIONS COMMISSION (FCC) PART 15 STATEMENT NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
Page 110
VISTA-32FB/VISTA-128FB Installation and Setup Guide CANADIAN EMISSIONS STATEMENTS This Class B digital apparatus complies with Canadian ICES-003 NOTICE AVIS The Industry Canada Label identifies certified L’é tiquette d’Industrie Canada identifie equipment. This certification means that the maté riel homologué . Cette é tiquette certifie que le equipment meets telecommunications network maté...
A P P E N D I X Summary of System Commands x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x User Code Add A User Code = User Code + 8 + New User Number + New User’s Code Commands...
Page 112
VISTA-32FB/VISTA-128FB Installation and Setup Guide Activate Access Relay for Current Partition = User Code + 0. Access Control Commands Request to Enter/Exit = User Code + [#] + 73. Request to Enter/Exit at Access Point = User Code + [#] + 74 + Access Point Number. Change Access Point State = User Code + [#] + 75 + Access Point + State.
10ma. Bad line when both voltage and current below these levels. Formats: ADEMCO High Speed, ADEMCO 4 + 2 Express, ADEMCO Low Speed, ADEMCO Contact ID, Sescoa and Radionics Low Speed Agency Listings: Burglary: UL609 Grade A Local Mercantile Premises and Mercantile Safe and Vault.
Page 114
VISTA-32FB/VISTA-128FB Installation and Setup Guide Remote Keypads 6139(R) 6160CR Physical: Physical: Width: 6.25 inches Width: 7.437 inches Height: 4.75 inches Height: 5.25 inches Depth: 1.25 inches Depth: 1.312 inches Electrical: Electrical: Voltage Input: 12VDC Voltage Input: 12VDC Current Drain: 100mA Current Drain: 150mA Interface Wiring:...
A P P E N D I X Contact ID Event Codes x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x TABLE OF CONTACT ID EVENT CODES Code Definition...
Page 116
VISTA-32FB/VISTA-128FB Installation and Setup Guide...
Adding a User Code ............9-3 #93 Menu Mode Programming Commands....4-4 Adding an RF Key to a User Code ........ 9-4 12/24 Hour Type Stamp Format ........5-11 ADEMCO 4+2 Express ..........3-7 1361 ................3-29 ADEMCO 4+2 EXPRESS..........C-1 1451 Transformer............C-1 ADEMCO 4146 ............
Page 118
VISTA-32FB/VISTA-128FB Installation and Setup Guide Burglary Features on Partition 1 Enable...... 5-15 Display Burglary & Panic Alarms for Other Partitions.. 5-13 Burglary Trigger for Response Type 8 ......5-2 Display Fire Alarms of Other Partitions ....... 5-13 Burglary Walk Test ............10-2 Display Troubles of Other Partitions......
Page 119
Index Fire With Verification Type 16 ........4-6 LINE SEIZE..............C-1 First Communication ............. 7-2 List of Figures..............vi First Test Report Time........... 5-6 LO BAT ............... 10-4 Force Arm..............6-1 Lobby Partition .............. 5-7 Force Arm Enable for Auto-Arm ........5-12 Log First Maintenance Signal........
Page 120
VISTA-32FB/VISTA-128FB Installation and Setup Guide Relay Timeout YYY Seconds ........5-11 REPORT CODE PROG ..........4-3 Reporting Formats............3-7 PABX Access Code............5-3 Request to Exit (RTE) Type 12 ........4-7 Pager ID Number for Alarms ......... 5-5 Reset on Second OFF for Bell 1 ......... 5-14 Pager ID Number for Bypasses........
Page 121
Index User Scheduling Menu Mode ........6-13 Users................2-1 Using ACS Zone Inputs..........4-8 Telco Handoff ..............7-3 Telephone Line Connections......... 3-7 Telephone Line Supervision .......... 3-7 TELEPHONE OPERATIONAL PROBLEMS ....A-3 Temporal Siren Pulse............ 5-1 View Capabilities ............9-1 Temporary Schedule .............
VISTA-32FB/VISTA-128FB Installation and Setup Guide WARNING! THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced wireless security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a vari- ety of reasons.
Seller shall have no obligation under this Limited Warranty or otherwise if the product is altered or improperly repaired or serviced by anyone other than ADEMCO factory service. For warranty service, return product transportation prepaid, to ADEMCO Factory Service, 170 Michael Drive, Syosset, New York 11791.
Need help?
Do you have a question about the Vista-32FB and is the answer not in the manual?
Questions and answers
can I bypass Check 974 Dialer 1
The provided context does not contain information on bypassing "Check 974 Dialer 1" on the ADEMCO Vista-32FB.
This answer is automatically generated