ADEMCO VISTA-128B Installation And Setup Gude page 116

Partitioned security system with scheduling
Hide thumbs Also See for VISTA-128B:
Table of Contents

Advertisement

VISTA-128B Installation and Setup Guide
*14
ZONE 9 RESPONSE TIME
Enter 1 to set fast response mode (10 msec) for appropriate devices wired to zone 9.
Enter 0 for normal response (350 msec). Must be 0 for UL.
*15
KEYSWITCH ASSIGNMENT
Enter the partition number 1-8 in which the keyswitch is being used. Otherwise, enter
0.
Requires the use of zone 7 wired loop (zone 7 is no longer available as protection zone
when used for keyswitch operation). If the keyswitch is used, the fire and panic alarm
voltage triggers automatically become ARMING and READY status outputs for support
of the Keyswitch LEDs.
Reports openings/closing by user "0" if reporting is enabled in field *40.
*16
CONFIRMATION OF ARMING DING (part.-specific)
Enter 1 to enable 1/2 second external alarm sounding ("ding") at the end of exit delay (or
after kissoff from the central station, if sending closing reports). Otherwise enter 0.
Must be 1 for UL commercial burglary installations. Bell test on arming is required in
UL commercial burglary installations.
*17
AC LOSS KEYPAD SOUNDING
Enter 1 to enable sounding at the keypad (rapid beeping) when AC power is lost
(sounding occurs about 2 minutes after actual AC loss).
Enter 0 if no AC power loss keypad sounding is desired.
*19
RANDOMIZE AC LOSS REPORT
Selecting this option helps prevent an overload of AC loss messages at the central
station during a community blackout.
Enter 1 to randomize AC loss reporting between 10 and 40 min. after an actual AC loss.
Enter 2 for 6-12 hours after AC loss. Enter 0 for normal AC loss reporting (about 2
minutes after actual AC loss).
*20
VIP MODULE PHONE CODE
If a 4285/4286 Voice Module is being used, enter the 2-digit phone code used to access
the system.
Enter 01-09 for first digit, and enter 11 (for
To disable the voice module, enter 00 for the 1st digit and enter 11 for the 2nd digit of
the code (disable code = 00,11). Must be disabled for commercial fire and UL
commercial burglary installations.
*21
PREVENT FIRE TIMEOUT
Enter 1 to disable (no timeout) the alarm sounder duration for any zone designated as a
fire zone, regardless of partition, so that fire sounding continues until the system is
reset.
Enter 0 if the normal burglary sounder duration (programmed in partition-specific field
*13) should apply to fire alarms.
*22
KEYPAD PANIC ENABLES (partition-specific)
Enter 1 to enable the appropriate keypad panics used in this partition.
Otherwise enter 0.
22-2
[00, 11]
) or 12 (for #) for second digit.
[0]
[0]
[0]
[0]
[0]
|
|
[0]
[001]
|
|
95
96
99