Output Devices; General Information - ADEMCO VISTA-128B Installation And Setup Gude

Partitioned security system with scheduling
Hide thumbs Also See for VISTA-128B:
Table of Contents

Advertisement

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
In This Section

General Information

Installing the 4204 and 4204CF Relay Modules
Installing the FSA Modules
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
General Information
The VISTA-128B supports up to 96 outputs to activate and de-activate as desired. Each
device must be programmed as to how to act (ACTION), when to activate (START), and when
to deactivate (STOP). Each of these is described later in this section. This is provided by
4204, 4204CF, FSA-8, FSA-24, 4140SN and/or Powerline Carrier devices.
They can be used to:
• Turn lights on and off
• Control sounders
• Control doors
• Give status indications.
4204/4204CF Relay Modules
Each 4204 module provides 4 relays with Form C (normally open and normally closed)
contacts. Each 4204CF module adds two additional style Y supervised bell outputs to the
system. If 4204CF modules are used exclusively, only relays 1 and 3 on each module can be
programmed. The other 2 relays (relays 2 and 4) on each module are used for supervision
purposes.
FSA Modules
The 8-Zone LED Fire System Annunciator FSA-8 and 24-Zone LED Fire System Annunciator
FSA-24 provide the ability for a fire response unit to identify quickly and easily the
point/zone of a fire. These indicators may be used for other functions as well, such as status
indication. A maximum of 4 FSA modules, in any combination, can be supported. Each FSA
module can support up to 24 LEDs dependent upon model selection.
4101SN Relay Modules
The 4101SN V-Plex Single Output Relay Module is a serial number polling loop output
device. The 4101SN features the following:
Form C relay contacts rated at 2A, 28VAC/VDC with contact supervision.
The position of the relay is supervised, but not the actual external contact wiring.
S E C T I O N

Output Devices

Wiring the 4300 Transformer
Programming Output Devices
9
9-1

Advertisement

Table of Contents
loading

Table of Contents