Wiring the 4100APG

The 4100APG may be used either with or without a serial printer. The 4100APG connects to
the VISTA-128B via the 4100SM. The 4100SM connects to the J8 connector on the control
via the 4142TR Cable.
Without the Event Log Printer
Connecting the 4100SM to the Control:
To connect the 4100SM to the control, perform the following steps:
Step
1
2
3
4
5
Connecting the 4100APG to the 4100SM
To connect the 4100APG to the 4100SM, perform the following steps:
Step
1
2
3
17-2
Action
Connect the 4142TR to J8 on the control. See figure 17-1.
Connect the RED wire of 4142TR to TB1-6 of 4100SM (RxD).
Connect the VIOLET wire of 4142TR to TB1-1 of 4100SM (DTR).
Connect TB1-7 of 4100SM to terminal 7 (Auxiliary Power -) of the control.
Connect TB1-8 of 4100SM to terminal 6 (Auxiliary Power +) of the control
Action
Connect the Incoming telephone line to the 4100APG RJ11 connector labeled
LINE. See figure 17-1.
(Optional) Connect the Handset side of telephone line to 4100APG RJ11 connector
labeled PHONE.
Connect the DB25M to DB-9M Cable (supplied), from 4100SM (25 pin) to
4100APG (9 pin) connector labeled SERIAL PORT INPUT.
6 7
Aux. Pwr
Aux. Gnd

Figure 17-1: Wiring the 4100APG Without the Serial Printer

J8
4100SM
Red
8
Black
7
RxD
6
5
4
3
2
1
DB-25
4100APG
DB-9
Serial Port Input
RJ-11
Line
To Telco